3P225748-4G English
6
3
Setting
Filter Auto Clean
Filter Auto Clean
12:00
A
– 3:00
A
• The period will change whenever
buttons are pushed in
the Clock setting screen for filter auto-cleaning.
12:00
A
–3:00
A
,
3:00
A
–6:00
A
,
6:00
A
–9:00
A
,
9:00
A
–12:00
P
,
12:00
P
–3:00
P
,
3:00
P
–6: 00
P
,
6:00
P
–9:00
P
,
9:00
P
–12:00
A
.
Select the desired period from the ones displayed.
• Push Menu/OK button.
The settings confirmation screen will appear.
4
Setting
Save the settings?
Filter Auto Clean
Yes
No
• Push button to select
Yes
on the settings confirmation
screen.
Push Menu/OK button to set the filter auto clean and return
to the basic screen.
NOTE
The filter auto clean function takes around 10 minutes.
Execution of the cleaning function, always during the scheduled time slot of 0 to 3 hours, will start as soon as
possible considering the following conditions:
• during the first hour
the cleaning function will only be performed during thermostat OFF intervals or when the unit is not operating;
• during the second hour
same condition as during first hour or when cooling or heating demand is rather low;
• during the third hour
the unit forces execution of the cleaning function, even when the unit is operating. After completion of the
cleaning function, the unit will start normal operation again.
The unit will try to perform the cleaning function during the next scheduled time slot of 3 hours in case it was not
executed.
If the unit, in case of VRV, could not perform the cleaning function after elapse of 2 consecutive scheduled time
slots of 3 hours, error code AH09 displays on the remote controller (Refer to “NOTE” on page 16). The error
code remains displayed as long as the function is not completed, but the unit can operate normally at all times.
Filter Auto-cleaning
The product has the following two operation modes, any one of which can be set for filter auto-cleaning.
Operation
mode
Description
Clock
setting
Availability for designating
time to start filter auto-
cleaning
Scheduled timer
operation
Performs filter auto-cleaning during the
designated period selected from eight periods.
(Factory default setting (12:00
A
-3:00
A
))
Auto control
operation
Performs filter auto-cleaning according to the
control reference.
or
Filter Auto-cleaning