3P155845-5H English

(Example)

If the time to clean air filter is set to “Filter Contamination-Heavy”, set Mode No. to “10”, FIRST CODE 

NO. to “0”, and SECOND CODE NO. to “02”.

MODE 

NO.

FIRST 
CODE 

NO.

DESCRIPTION OF SETTING

SECOND CODE NO.      NOTE)

01

02

03

10

0

Filter Contamination-
Heavy/Light (Setting 
for spacing time 
of display time 

to clean air filter) 

(Setting for when 

filter contamination is 

heavy, and spacing 
time of display time to 

clean air filter is to be 

halved)

Long-life 

type

light

approx. 

2,500 
hours

heavy

approx. 

1,250 
hours

-

3

Spacing time of display time to 

clean air filter count (Setting for 
when the filter sign is not to be 

displayed)

Display

Do not display

-

12

(VRV 

system)

1

ON/OFF input from outside (Set 
to enable starting/stopping from 
remote.)

Forced OFF input

ON/OFF

-

2

Thermostat differential 
changeover (Set when using 
remote controller thermostat 
sensor.)

1°F

0.5°F

-

13

1

Selection of Air Flow Direction 
(Setting for when a sealing 
member of air discharge outlet 
kit has been installed)

F

T

W

4

Air Flow Direction Range Setting

Upper

Normal

Lower

NOTE 

• 

The SECOND CODE NO. is factory set to “01”. However, for the following cases it is set to “02”.

• 

Air Flow Direction Range Setting

Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial settings for all the indoor units of the group are 
equal. (For group control, refer to the installation manual attached to the indoor unit for group control.)

Summary of Contents for BRC7E830

Page 1: ...INSTALLATION MANUAL MODEL BRC7E830 English 3P155845 5H Wireless Remote Controller Kit READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE...

Page 2: ...unsafe practices NOTE Indication situation that may result in equipment or property damage only accidents WARNING Perform installation work in accordance with this installation manual Improper instal...

Page 3: ...1 2 3 1 2 3 1 2 3 2 2 NOTE TO THE INSTALLER Be sure to instruct the customer how to properly operate the system showing him her the attached operation manual 3 REMOTE CONTROLLER INSTALLATION Installin...

Page 4: ...e suction grille and the air filter according to the instructions in the installation manual attached to the decoration panel 3 Remove the control box cover according to the instructions in the instal...

Page 5: ...emote controller 1 Hold down the button and the TEST button for at least 4 seconds to get the Field Set mode Indicated in the display area in the figure at right 2 Press the FAN button and select a mu...

Page 6: ...unit and the indication of the remote controller display occurs b Multi System Operations remain displayed shortly after execution Since the indication of the remote controller is turned off no discre...

Page 7: ...decoration panel 4 Connect the harness from the receiver to the connector X1A on the transmitter board X2A X1A After connecting use the attached clamp to fix the two harnesses to the transmitter boar...

Page 8: ...the indoor unit the indoor unit setting may have to be changed Refer to the installation manual for each optional accessory Procedure 1 When in the normal mode press the TEST button for a minimum of f...

Page 9: ...to be displayed Display Do not display 12 VRV system 1 ON OFF input from outside Set to enable starting stopping from remote Forced OFF input ON OFF 2 Thermostat differential changeover Set when using...

Page 10: ...or unit if it does not operate 2 Refer to the installation manual attached to the outdoor unit for individual operation system types Order Operation 1 Open gas side stop valve 2 Open liquid side stop...

Page 11: ...10 3P155845 5H English...

Page 12: ...3P155845 5H EM12A032 1211 DE...

Reviews: