Installation manual BRC1E52B7

15

 

4PW72364-1 – 11.2011

Mode 

No.

Note) 1

FIRST 

 CODE 

 NO.

Description of setting

SECOND CODE NO.  Note) 2

01

02

03

04

12 (22)

1

ON/OFF input from outside (setting 

for when forced ON/OFF is to be 

operated from outside).

Forced OFF

ON/OFF 

operation

2

Thermostat differential changeover 

(setting for when using remote 

sensor).

1°C

0.5°C

13 (23)

0

High air outlet velocity (for high 

ceiling applications).

≤ 

2.7m

> 2.7 

 3.0m

> 3.0 

 3.5m

1

Selection of airflow direction (setting 

for when a blocking pad kit has 

been installed).

4-way flow

3-way flow

2-way flow

3

Selection of airflow function (setting 

for when using a decoration panel 

for outlet).

Equipped

Not equipped

4

Airflow direction range setting.

Upper

Normal

Lower

6

Setting the external static pressure 

(setting according to the connected 

 duct resistance) (for FHYK, follow 

the high ceiling setting)

Normal

High static 

pressure

Low static 

pressure

(Normal)

(High ceiling)

15 (25)

3

Drain pump operation with 

humidifying.

Equipped

Not equipped

1c

1

Thermostat sensor in remote 

controller (for Auto mode and 

Setback function only)

Not use

Use

1e

2

Setback function

Not use

Heat only

Cool only

Cool and 

Heat

Notes)

1. 

Though setting is performed totally in the group, set Mode No. in the parenthesis when 

individual setting per indoor unit or checking after the setting should be performed. 

2. 

SECOND CODE NO. at factory shipment is set to "01". However for the following 

cases it is set to "02".

 

● Airflow direction range setting (except round flow cassette)

 

● Thermostat sensor in remote controller (SkyAir only)

 

● Thermostat sensor in remote controller for auto mode operation and Setback 

function only

3. 

Any function which the indoor unit does not have is not displayed.

Summary of Contents for BRC1E52B7

Page 1: ...Be sure to read this installation manual before conducting the installation of this product BRC1E52B7 WIRED REMOTE CONTROLLER INSTALLATION MANUAL...

Page 2: ...ions and menu items of remote controller buttons 10 5 Power on 12 6 Field settings 13 7 Test operation method in the case of SkyAir 16 8 Checking procedure of Error History 19 9 Registration method of...

Page 3: ...regarding relocation and reinstallation of the remote controller Improper installation work may result in leakage electric shocks or fire hazards Install the remote controller in accordance with the i...

Page 4: ...Corroding of copper pipes or soldered parts may result in refrigerant leakage 3 Near machinery emitting electromagnetic radiation Electromagnetic radiation may disturb the operation of the control sys...

Page 5: ...hole to the center of the wiring through hole on the controller lower case when making the hole 8 10 External view of the remote controller Through hole 8 10 Lower case Through hole 48 5 40 3 3 Remove...

Page 6: ...e burr with a file or the like 3 4 3 Upper outlet 3 4 4 Upper center outlet Cut off thin area hatched area with nippers or the like and then remove burr with a file or the like Cut off thin area hatch...

Page 7: ...of two wires Sheath stripping length 150 mm for upper outlet 200 mm for upper center outlet Connect the terminals P P1 N P2 of the remote controller upper case with the terminals P1 P2 of the indoor u...

Page 8: ...t P1P2 3 5 3 Upper outlet Install attached wiring retainer to prevent wiring pinch according to left figure PC board Indoor unit Wiring retainer Wiring retainer Upper case Lower case Upper case Wiring...

Page 9: ...lower case In the case of wiring center upward drawing or rearward drawing see wiring procedure first as wiring with the case is needed before fixing 3 6 1 In the case of installation on the wall Sec...

Page 10: ...ect flat place for installation face as possible And do not tighten the installation screws too much not to deform the lower case CAUTION 3 7 Install the upper case as original condition Align the upp...

Page 11: ...anguage Depending on connected model 4 Up button Used to raise the set temperature The next items on the upper side will be highlighted The highlighted items will be scrolled continuously when the but...

Page 12: ...or unit AirNet Address Outdoor unit AirNet Address Error History Indoor Unit Status Outdoor Unit Status Forced Fan ON Switch Main Sub Controller Filter Indicator Test Filter Auto Clean Brush Filter In...

Page 13: ...controlled by two remote controllers Error code U5 is displayed in the connection checking screen Select the sub remote controller by pressing the Operation mode selector button of either one of the r...

Page 14: ...SECOND CODE NO of the FIRST CODE NO to be changed and select desired SECOND CODE NO by using Up Down button Multiple identical mode number settings are available In the case of group setting all of S...

Page 15: ...COND CODE NO Note 2 01 02 03 04 10 20 0 Filter Contamination Heavy Light Setting for spacing time of display time to clean air filter Setting for when filter contamination is heavy and spacing time of...

Page 16: ...c pressure setting according to the connected duct resistance for FHYK follow the high ceiling setting Normal High static pressure Low static pressure Normal High ceiling 15 25 3 Drain pump operation...

Page 17: ...k After air purge by vacuum pump refrigerant pressure may not rise even though the stop valve is opened The reason is that refriger ant system of the outdoor unit is blocked by electrical expansion va...

Page 18: ...test operation finishes If interior work is not completed after the test operation finish explain to the customer that operation should not be performed until the interior work comple tion to protect...

Page 19: ...the indoor unit After the failure diagnosis finishes press and hold On Off button for 4 seconds or longer in the Mainte nance Information screen to erase the error code record Failure diagnosis metho...

Page 20: ...ic screen Service Settings menu is displayed 8 2 Select Error History in the Service Settings menu and press Menu Enter button The Error History menu screen is displayed 8 3 Select RC Error History in...

Page 21: ...ter button Setting confirmation screen is displayed 9 6 Select Yes and press Menu Enter button Setting details are determined and Service Settings menu screen returns 9 7 Press Cancel button once The...

Page 22: ...Enter button 10 2 Press Cancel button twice The basic screen returns Basic screen 10 1 Cool Set to Cool 28 C Press Menu Enter button Main menu screen Return Setting Main Menu Quick Start Ventilation E...

Page 23: ...ric changes continuously Day of the week is set automatically 11 4 Press Menu Enter button Setting confirmation screen is displayed 11 5 Select Yes and press Menu Enter button Setting details are conf...

Page 24: ...ss Up Down buttons to select Language on the Language screen English Deutsch Shqip Hrvatski esky Magyar Rom n Srpski Sloven ina Sloven ina Pressing Menu Enter button Setting details are confirmed and...

Page 25: ...unit Make sure that this controller is set to main factory set first change the restrictions to the setting you prefer and only then set the remote controller to sub 13 7 To lock menu button in basic...

Page 26: ...s sub start with only connecting this controller to the unit Make sure that this controller is set to main factory set first change the restrictions to the setting you prefer and only then set the rem...

Page 27: ......

Page 28: ...Copyright 2011 Daikin 4PW72364 1 11 2011...

Reviews: