Installation manual BRC1E52B7
15
4PW72364-1 – 11.2011
Mode
No.
Note) 1
FIRST
CODE
NO.
Description of setting
SECOND CODE NO. Note) 2
01
02
03
04
12 (22)
1
ON/OFF input from outside (setting
for when forced ON/OFF is to be
operated from outside).
Forced OFF
ON/OFF
operation
—
—
2
Thermostat differential changeover
(setting for when using remote
sensor).
1°C
0.5°C
—
—
13 (23)
0
High air outlet velocity (for high
ceiling applications).
≤
2.7m
> 2.7
≥
3.0m
> 3.0
≥
3.5m
—
1
Selection of airflow direction (setting
for when a blocking pad kit has
been installed).
4-way flow
3-way flow
2-way flow
—
3
Selection of airflow function (setting
for when using a decoration panel
for outlet).
Equipped
Not equipped
—
—
4
Airflow direction range setting.
Upper
Normal
Lower
—
6
Setting the external static pressure
(setting according to the connected
duct resistance) (for FHYK, follow
the high ceiling setting)
Normal
High static
pressure
Low static
pressure
—
(Normal)
(High ceiling)
—
—
15 (25)
3
Drain pump operation with
humidifying.
Equipped
Not equipped
—
—
1c
1
Thermostat sensor in remote
controller (for Auto mode and
Setback function only)
Not use
Use
—
—
1e
2
Setback function
Not use
Heat only
Cool only
Cool and
Heat
Notes)
1.
Though setting is performed totally in the group, set Mode No. in the parenthesis when
individual setting per indoor unit or checking after the setting should be performed.
2.
SECOND CODE NO. at factory shipment is set to "01". However for the following
cases it is set to "02".
● Airflow direction range setting (except round flow cassette)
● Thermostat sensor in remote controller (SkyAir only)
● Thermostat sensor in remote controller for auto mode operation and Setback
function only
3.
Any function which the indoor unit does not have is not displayed.