Daikin BRC1D71 Installation Manual Download Page 7

 

 

 

BRC1D71
Remote controller
3P166742-2

Installation manual

 

5

 

Mode 

No.

Note 1

FIRST 
CODE 

NO.

Description of setting

SECOND CODE NO. Note 2

01

02

03

04

 

10(20)

0

 

Filter Contamination - Heavy/Light
(Setting for spacing time of display time 
to clean air filter)
(Setting for when filter contamination is 
heavy, and spacing time of display time to 
clean air filter is to be halved)

 

Ultra long 

life filter

Approx. 

10.000 

hrs.

Approx. 

5.000 

hrs.

Long life

 filter

Approx. 

2.500 

hrs.

Approx. 

1.250 

hrs.

Standard 

filter

Approx. 

200 hrs.

Approx. 

100 hrs.

1

 

Long-life filter type (setting of filter sign indication 
time). (Change setting when ultra-long filter is 
installed)

 

Long-life 

filter

Ultra-long life 

filter

2

 

Thermostat sensor in remote controller

 

Use

Not use

3

 

Spacing time of display time to clean air filter count 
(setting for when the filter sign is not to be displayed)

 

Display

Do not 

display

12(22)

1

 

ON/OFF input from outside (setting for when forced 
ON/OFF is to be operated from outside).

 

Forced OFF

ON/OFF 

operation

2

 

Thermostat differential changeover (setting for when 
using remote sensor).

 

2°F

1°F

13(23)

3

 

Selection of air flow function (setting for when using 
a decoration panel for outlet).

 

Equipped

Not 

equipped

4

 

Air flow direction range setting.

 

Upper

Normal

Lower

15(25)

3

 

Drain pump operation with humidifying.

 

Equipped

Not 

equipped

1b

0

 

Permission level setting

 

Level 2

Level 3

1

 

Away function

 

Not  permitted

 

Permitted

2

 

Thermostat sensor in remote controller (for limit 
operation and away function only)

 

Use

Not use

Light

Hea

vy