Daikin BACnet MT3041 Installation And Maintenance Manual Download Page 7

Integration

www.DaikinApplied.com 

IM 916-5 • MICROTECH COMMUNICATION MODULE

Configuring the BACnet 

Communication Module

The following section describes how to configure the BACnet 

IP communication module for BAS network integration. Follow 

these instructions to set addressing parameters for the BACnet 

communication module using the unit controller display menu.  

Configuration varies depending on the structure of your 

network and BACnet broadcasting requirements for IP subnets.

NOTE: 

Refer to MicroTech 4 Rebel Applied Unit Controller 

Operation Manual (OM 1303) or MicroTech III Applied 

Air Handling Unit Controller Operation Manual 

(OM 920) for default values and keypad operating 

instructions. Refer to the respective Unit Controller 

Integration Guide for all BACnet objects and other 

network communication information. Se

Reference 

Documents

 for literature descriptions and locations.

BACnet IP Addressing

There are three parameters that must be configured properly 

to establish communication between the unit controller and the 

BACnet IP network: BACnet IP Address, IP Subnet Mask, and 

IP Router Address. See your system integrator for additional 

information regarding BACnet IP addressing. 
The BACnet communication module is DHCP (Dynamic Host 

Configuration Protocol) enabled. See 

Appendix A: BACnet IP 

Networks

 for more information about IP network types.

To Configure the Module using the Unit 

Controller Display Menu:

1.  Navigate to the Enter Password screen if you have 

not already entered a password. If you have entered a 

password, skip to step 3. 

2. 

Enter Password: 6363.

3.  Continue to navigate to the BMS Communications\

BACnet IP Set-Up menu. 

NOTE: 

The IP Setup menu only appears if a BACnet 

communication module installed correctly. If the 

BACnet communication module is installed correctly 

and this menu still does not appear, cycle power to 

the unit controller and repeat the procedure from Step 

3 above. 

4.  Modify the parameters as necessary. See 

Table 3

 for 

details.

5. 

To modify the Given IP Address, Given IP Mask, or Given 

IP Gateway, follow steps a-c below:

a. 

Fully change all four octets of the desired field.

NOTE: 

After entering all four octets of the desired field, the 

cursor should blink in the open space to the right of 

the last character of the octet.

b.  Select Enter by pressing down on the circular knob 

on the unit controller keypad. 

Do not press the 

Back button until Enter has been selected.

c. 

From this screen, use the Back button to navigate 

to the BMS Communications\BACnet IP Set-Up 

menu and change “ApplyIPChgs” from No to Yes.

6. 

Check that the network cable is connected and navigate 

to the IP Setup menu to verify the Actual IP Address. The 

Actual IP Address displays 0.0.0.0 if the network cable 

is not attached. This procedure may take a minute while 

the BACnet communication module powers up.

Configurable Parameters

Table 3

 defines the network parameters of the BACnet 

communication module that must be set using the unit 

controller display menu in order to establish communication 

between the unit controller and the BAS. Change parameters 

as required for your network. 

NOTE: 

To save alteration of these parameters, select 

“ApplyIPChgs” under 

the BMS Communications\

BACnet IP Set-Up menu (see Step 5 from previous 

section).

Summary of Contents for BACnet MT3041

Page 1: ...Controls Part Number IM 916 Date August 2020 BACnet IP Communication Module for MicroTech III and MicroTech 4 Unit Controllers Applied Rooftop Systems and Self Contained Units Models DPS DPH MPS RAH...

Page 2: ...ht Emitting Diodes LEDs 5 BACnet Network Connector 5 Board to Board Connector 5 Installation 6 Installation and Mounting 6 Field Installation Kit 6 Installing a new Communication Module 6 Replacing a...

Page 3: ...ath or serious injury if not avoided NOTICE Notices give important information concerning a process procedure special handling or equipment attributes Revision History IM 916 Oct 2008 Initial release...

Page 4: ...ture numbers and locations Specifications General Dimensions W x H x D 1 77 x 4 33 x 2 95 in 45 x 110 x 75 mm Weight 3 5 oz 98 g Material Base plastic pigeon blue Housing plastic light gray Operating...

Page 5: ...lashing with 2Hz Software error1 Red Hardware error1 1 In the event that this should occur cycle power to the unit controller to attempt to clear the problem Contact the Controls Customer Support Grou...

Page 6: ...tool to the tab on the bottom of the unit controller and pull the screwdriver away from the controller 5 Carefully remove the blue plastic knockout on the far right side of the BACnet communication m...

Page 7: ...tered a password skip to step 3 2 Enter Password 6363 3 Continue to navigate to the BMS Communications BACnet IP Set Up menu NOTE The IP Setup menu only appears if a BACnet communication module instal...

Page 8: ...t Mask Gvn Msk provided the network is connected when Apply Changes is set to Yes Act Gwy If DHCP set to On Address automatically assigned by network If DHCP set to Off Address Given Gateway Address A...

Page 9: ...nfirm that the DHCP parameter is set to Off when a static IP address is being used for non DHCP networks Check that the defined UDP port e g BAC0 is open in the firewall Verify if BBMDs are required B...

Page 10: ...dentifier or their BACnet address The IP address is part of the BACnet address and may not be changed for the alarm recipient For this reason option Device Object Identifier must always be used Access...

Page 11: ......

Page 12: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representativ...

Reviews: