12 Technical data
Installer reference guide
40
AZQS100~14 AZQS100~140B7Y1B
Split system air conditioners
4P3855291 – 2014.08
AZQS100_Y1
AZQS125_Y1
AZQS140_Y1
Liquid
Quantity
1
Type
Flare connection
Diameter (OD)
Ø9.52 mm
Gas
Quantity
1
Type
Flare connection
Diameter (OD)
Ø15.9 mm
Drain
Quantity
5
Type
Hole
Diameter (OD)
Ø26 mm
Piping length
Minimum
5 m
Maximum
50 m
Equivalent
70 m
Chargeless
30 m
Additional refrigerant charge
See "To determine the additional refrigerant amount"
Maximum height difference between outdoor
unit and indoor unit
30 m
Maximum interunit level difference
0.5 m
Heat insulation
Both liquid and gas pipes
Defrost method
Reverse cycle
Defrost control
Sensor for outdoor heat exchanger temperature
Capacity control method
Invertercontrolled
Capacity control
Cooling
Minimum
Maximum
Heating
Minimum
Maximum
Safety devices
High pressure switch / fan motor thermal protector / fuse
Standard accessories
1 installation manual / 2 tie wraps
Electrical specifications: AZQS_Y1
AZQS100_Y1
AZQS125_Y1
AZQS140_Y1
Power supply
Name
Y1
Phase
3N~
Frequency
50 Hz
Voltage
380415 V
Voltage range
Minimum
342 V
Maximum
456 V
Current
Nominal running current
Starting current
Z
max
Complies to EN 61000311
Maximum running current
Recommended fuses
16 A
20 A
25 A
Wiring connections
For power supply
See "Connecting the electrical wiring"
For connection with indoor
Power supply intake
Outdoor unit only