background image

IM 817-7 

40 www.DaikinApplied.com

 NOTICE

Typical conditions - 95ºF ambient, 75 psig suction, 285 psig head 

pressure, 6 - 7º superheat, 15ºF subcooling

Superheat Adjustment

1 . 

Remove the seal cap from thermal expansion valve 

(see 

Figure 99

).

2 . 

Turn the adjustment screw clockwise to increase 

superheat and counterclockwise to decrease 

superheat (

Figure 99

). One complete 360° turn 

changes the superheat approximately 3-4°F, 

regardless of the refrigerant type. As much as 30 

minutes may be required for the system to stabilize 

after the adjustment is made.

3 .  

Replace and hand-tighten seal cap.

 CAUTION

Do not force adjustment stem of TXV. When adjusting superheat 

setting, there are a maximum of 10 turns on the stem. Turning 

adjustment stem after reaching stop will damage valve.

Figure 99: Superheat Adjustment of TXV

Superheat

Adjustment Screw

Counterclockwise To 

Decrease Superheat

Clockwise To Increase 

Superheat

Remove Seal Cap

Making Control Connections

MicroTech Unit Mounted DDC 

Control Components – Models 

AVS, AVV, and AVR

Note: 

Refer to 

Figure 101 on page 42.

MicroTech Unit Ventilator Controller (UVC): 

(Located 

Beneath the Local User Interface Panel). Factory 

mounted and run tested, microprocessor-based 

DDC control device capable of complete Standalone 

unit control, Client/Server control or incorporated 

into a building-wide network using an optional plug-

in communication module. The UVC contains a 

microprocessor that is preprogrammed with the 

application code required to operate the unit. The UVC 

supports up to 16 analog inputs, 8 binary inputs, 4 

analog outputs, 2 PWM outputs, and 14 binary outputs. 

The UVC EXP I/O board supports up to 4 additional 

analog inputs and 8 additional binary outputs. Client/

Server units have the controller factory configured 

and installed for a local peer-to-peer network between 

these units (network wiring between these units needs 

to be field installed). Optional network communication 

is provided via plug-in communication modules that 

connect directly to the UVC.

Communication Module (optional):

 Plug-in network 

communication module that is attached to the UVC 

via a 8-pin header and 4 locking standoffs. Available 

communication modules:

 • 

Building Automation and Control Network 

(BACnet®) Client Server/Token Passing 

(MS/TP)

 – Allows the UVC to inter-operate 

with systems that use the BACnet (MS/TP) 

protocol with a conformance level of 3. Meets 

the requirements of ANSI/ASHRAE 135-2008 

standard for BACnet systems

 • 

l

on

W

orks

® compliant Space Comfort 

Controller (SCC)

 – Supports the 

L

on

W

orks

 SCC 

profile number 8500_10

Local User Interface (LUI) (optional):

 (see 

Figure 

100 on page 42

The LUI provides a unit mounted 

interface which indicates the current unit operating state 

and can be used to adjust the unit ventilator operating 

parameters (operating mode, temperature set points, 

fan speed and occupancy mode). The LUI features a 4 

x 20 OLED digit display, 4 keys, and 2 individual LED 

indicators. In addition to the operating mode states 

and fan functions, the touch pad will digitally display: 

 • 

The room set point temperature

 • 

The current room temperature

 • 

Any fault code for quick diagnostics at the unit

External Signal Connection Plugs:

 Three (3) 

multi-pin plugs are factory provided and pre-wired 

with short wire whips that are capped (they must 

remain capped if not used). Provided for field 

wiring of:

 • 

Remote Wall Mounted Temperature Sensor 

(optional accessory)

 • 

External Input Signals (by others) 

– 

Unoccupied, remote shutdown, ventilation lockout, 

dew point/humidity (night time operation), or 

exhaust interlock signals

 • 

External Output Options (by others)

 – Fault 

indication signal, exhaust fan on/off or auxiliary 

heat signal

Electric Connection Box:

 Contains the motor speed 

transformer. Refer to the unit wiring diagram for 

specifics.

Summary of Contents for AVV

Page 1: ...Maintenance Manual IM 817 7 Group WSHP Document PN 9102047358 Date October 2018 Daikin Classroom Unit Ventilators Floor Models AVS AVV AVB and AVR Digital Ready MicroTech Control J Vintage Field Cont...

Page 2: ...ondensate Piping 36 Unit Ventilator Split Systems Guidelines 37 Checking System Charge 38 Determining Subcooling 38 Determining System Superheat 39 Superheat Adjustment 40 Making Control Connections 4...

Page 3: ...c Heat 68 Steam Low Cap 13 6 Element Low Cap Electric Heat 69 Steam High Cap 65 1 Row HW 78 Opposite End Steam Low Cap 66 2 Row HW 79 Opposite End Steam High Cap 67 3 Row HW 00 None Hand Orientation 8...

Page 4: ...carrier since such damage is the carrier s responsibility Storage If equipment is stored for any length of time before installation it should remain in its shipping packaging in a clean dry climate co...

Page 5: ...ost serious hazards that will result in death or severe personal injury WARNING means the hazards can result in death or severe personal injury CAUTION identifies unsafe practices that can result in p...

Page 6: ...o the unit itself A weather tight seal keeps unwanted air and moisture from entering the occupied space See Figure 6 on page 7 through Figure 21 on page 11 and Table 2 on page 10 for various louver de...

Page 7: ...nd Vertical Blade Louvers Without Flanges With Grille or With Flange Without Grille Louver drain lip Grille Louver with weep hole Flange Flange Outside Air Vertical Louver with Flange without Grille H...

Page 8: ...intel By Others Accumulatedmoisturecancausepropertydamageifnotproperly drained Installing contractor must provide such drainage CAUTION Figure 11 Above Floor Level Outdoor Air Intake Using Arrangement...

Page 9: ...th High Louver Application Not More Than 28 711mm Sealed Cement Mortar Pitch Away From Unit Important Gasket sealing surface is required Louver Lintel By Others Piping Piping Floor Line Unit Configura...

Page 10: ...base is 1 25mm thick at the unit and tapers toward the louver The mortar at the unit also acts as a backing against which the open cell gasket of the unit itself can seal This is critical in preventi...

Page 11: ...Pitched Away from Unit Toward Louver Figure 21 Vertical or Horizontal Blade Wall Intake Louver Recessed Without Flange Horizontal Blade Shown Drain Holes Do Not Block With Mortar or Caulking Materials...

Page 12: ...while supporting the unit from the front until it is possible to slide skid out from under the unit GENTLY LOWER the rear of the unit to the floor 3 Figure 25 Removing Unit from Skid 1 Carefully slid...

Page 13: ...al power before servicing unit to prevent injury or death due to electrical shock DANGER Personal injury hazard Wear protective gloves to avoid possible cuts and abrasions from exposed edges Avoid con...

Page 14: ...llow Upper Plate Deep Lower Bracket Drain Pan Standard Drain Connection 1 4 hex head screws To Clean the Drain Pan 1 Remove the shallow and deep upper plates from the unit 2 Spray water into the drain...

Page 15: ...aulk Weep Holes Floor Unit Insulating Blanket Back Of Unit Unit Bottom Gasket Seal Under Unit Bird Screen Internal Column For Wall Bracing By Others Unit Gasket 1 End Panel w Cut Out Lintel by others...

Page 16: ...d chilled water supply and return system are thoroughly flushed and cleaned before connecting piping to the unit ventilator Debris in the lines can damage the unit For All Systems Be sure to install t...

Page 17: ...unions for future servicing by others Air Flow Figure 39 Protect Components From Overheating Before Brazing Use A Quenching Cloth When Brazing to Prevent Overheating The Piping Components Avoid Valve...

Page 18: ...zing valve and a 24 610mm long pressure equalizing line which terminates in a 1 2 M P T fitting 3 Steam hot water connections may be same end as cooling coil connections but they are recommended to be...

Page 19: ...ply and return connections 2 Steam coils have a factory installed pressure equalizing valve and a 24 610mm long pressure equalizing line which terminates in a 1 2 M P T fitting 3 Steam hot water conne...

Page 20: ...ent Plug HW DX Heating Right Hand R S 13 3 4 350mm A B J Air Flow Vent Plug HW DX 8 1 2 216mm S Supply R Return Direct Expansion and Steam Unit Note For opposite end drain steam coils code 78 79 Retur...

Page 21: ...e SL Suction Line LL SL J D C 7 1 4 184mm Air Flow 11 3 4 299mm Cooling Left Hand Table 6 Coil Connection Dimensions For Lettered Values1 Unit Depth Dimensions A B C D E F G H I J K in 16 5 8 3 3 4 12...

Page 22: ...bottom of unit and H 2 51mm from the back of unit Unless otherwise noted LH and RH connections are the same Figure 63 Direct Expansion Cooling Coils G 9 14 1 4 368mm J 10 1 8 257mm R S H K Air Flow J...

Page 23: ...ends Face Bypass End of Cycle Valves 2 Way End of Cylce Valve When piping the 2 Way End of Cycle valve refer to label to determine the direction of flow The valve should be installed so that there is...

Page 24: ...When using MicroTech controls they must be opposite end The End of Cycle valve accessory must be field installed on the unit for which it was selected Figure 70 3 Way EOC Valve Dimensions Connection C...

Page 25: ...osition Running Time Motor 95 sec Running Time Fail Safe 25 sec Ambient Humidity max 95 RH non condensing Ambient Temperature Range 22 F to 122 F 30 C to 50 C Storage Temperature Range 40 F to 176 F 4...

Page 26: ...ing Time Motor 95 sec Running Time Fail Safe 25 sec Ambient Humidity max 95 RH non condensing Ambient Temperature Range 22 F to 122 F 30 C to 50 C Storage Temperature Range 40 F to 176 F 40 C to 80 C...

Page 27: ...Running Time Motor 150 sec constant independent of load Running Time Fail Safe 25 sec 4 F to 122 F 20 C to 50 C 60 sec 22 F 30 C Ambient Temperature Range 22 F to 122 F 30 C to 50 C Storage Temperatu...

Page 28: ...Safe 25 sec Ambient Humidity max 95 RH non condensing Ambient Temperature Range 22 F to 122 F 30 C to 50 C Storage Temperature Range 40 F to 176 F 40 C to 80 C Table 25 3 Way Valve Body Specification...

Page 29: ...can begin to have any influence on the water flow through the coil The control system no matter how sophisticated cannot overcome this Oversized control valves can also result in hunting which will s...

Page 30: ...n provide unions for removal of the unit coil and or the control valve Heating Hot Water End of Cycle Valve Piping The 2 way End of Cycle hot water or 2 pipe CW HW valve is furnished normally open to...

Page 31: ...Return Balancing and Shutoff Valve Shutoff Valve Supply Supply 2 way EOC Valve Unit Coil Unions A B Note For Erie E O C water valves always have the direction of water flow piped to the B port of the...

Page 32: ...end as cooling coil connections but are recommended to be opposite end to facilitate piping When using Daikin factory controls they must be opposite end The modulating valve accessory must be field i...

Page 33: ...Note Left Hand Steam Supply and Right Hand Steam Return Shown Typical Steam Coil Piping Figure 86 Face and Bypass With 2 Way End of Cycle Valve Same End Drain Connection Piping Within Unit End Compar...

Page 34: ...pen Hot Water or 2 pipe CW HW Valve Piping typical The 2 way Modulating hot water or 2 pipe CW HW valve is furnished normally open to the coil When the valve is de energized off there is full flow thr...

Page 35: ...Figure 90 2 Way Modulating Valve Control Normally Closed Chilled Water Piping Return Return Balancing and Shutoff Valve Shutoff Valve Supply Supply 2 way Modu lating Valve Unit Coil Unions Figure 91 2...

Page 36: ...s of the material Likewise insulate the suction line See Figure 95 through Figure 98 for typical piping and wiring Ensure proper insulation of supply and return piping Proper insulation prevents loss...

Page 37: ...ncorporate Compressor Time Delay 5 minute in condensing unit control system reduces excessive compressor cycling see Figure 98 on page 39 Single phase compressors consider hard start kits to overcome...

Page 38: ...harge should be checked under design conditions 95 F outside air 80 F 67 F DB WB indoor air Refer to condensing unit manufacturer s guidelines Before adjusting refrigerant charge verify that the unit...

Page 39: ...cessary to adjust TXV to obtain correct superheat Table 32 Saturated Temperature Pressure Chart F R410A PSIG F R410A PSIG F R410A PSIG 32 101 1 44 127 7 80 235 8 33 103 2 45 130 2 85 254 7 34 105 2 46...

Page 40: ...a local peer to peer network between these units network wiring between these units needs to be field installed Optional network communication is provided via plug in communication modules that conne...

Page 41: ...ding Edge indoor outdoor true enthalpy comparison economizer The sensor is located in the outdoor air section of the unit before the outdoor air damper With network applications the unit mounted senso...

Page 42: ...trol Board Note If Installing Communication Module refer to the installation instructions specific to that Communication Module Figure 100 AV Top View 3 Figure 101 MicroTech Sensor and Component Locat...

Page 43: ...es for quick diagnostics at the unit The LUI has a built in menu structure Password protected with 4 keys and 2 individual LED indicators to adjust the unit ventilator operating parameters shown in th...

Page 44: ...IM 817 7 44 www DaikinApplied com Typical MicroTech Wiring 115Volt 60Hz 1 Phase Note See on page 45 for typical MicroTech service and disconnect wiring and wiring schematic legend...

Page 45: ...R4L Relay Fan Low Speed TBE Terminal Block Electric Heat FC FD Fuse Control Transformer R32 Relay Drain Pan Heater TR1 Transformer Motor Speed HP High Pressure Switch R28 Relay Outdoor Motor Air TR3 T...

Page 46: ...ventilator electric connection box to load side of unit power switch switch provided by Daikin The junction box has 1 25mm and 2 51mm knockouts located 10 1 2 267mm from right end of unit 3 Provide g...

Page 47: ...r sensor then placement of the Remote Wall Mounted Temperature Sensor is critical for proper room temperature sensing see Figure 107 and Figure 108 The UVC is capable of using one of four remote wall...

Page 48: ...at back of Local User Interface LUI Panel Plug for unit mounted sensor Sensor Functions Display sensor to show room Temperature fan speed AUTO HIGH MEDIUM LOW system mode HEAT COOL AUTO OFF ALARM Ove...

Page 49: ...cotton cloth Do not use any type of cleaner as it may damage the buttons or scratch the display Do not paint Terminations Daikin Applied recommends using shielded 22AWG for all connections and a sepa...

Page 50: ...or 910247453 Sensor 910247450 Description 24VAC Occupancy Shutdown Not Used Status LED Setpoint Unit Mode Fan Speed 10K RTD Ground Wire 908 907 906 909 912 901 902 911 910 Typical Wiring Terminal Labe...

Page 51: ...cuts out below 38 F 2 F and automatically resets above 45 F 2 F Responds when any 15 of the capillary length senses these temperatures Wired so that upon T6 cut out the outside air damper A1 closes t...

Page 52: ...IM 817 7 52 www DaikinApplied com Figure 112 Component Locations Vertical Floor Unit Shown 1 2 3 4 5 7 8 9 10 12 11 6 13 15 Outdoor Air Opening Sensor Motor...

Page 53: ...www DaikinApplied com 53 IM 817 7 Typical Wiring Diagram Digital Ready Face and Bypass Control CAUTION Refer to unit wiring diagram located on the right front panel for actual wiring...

Page 54: ...hm NTC sensor is constructed from stainless steel with an epoxy seal and twisted wire leads Type 10K ohm 25 C Accuracy 0 2 F 40 F 80 F 0 36 F 32 F 158 F 1 K ohm PTC Sensor The 1 K ohm sensor is a shri...

Page 55: ...Unit Ventilator Controller UVC A 4 to 20 mA input signal can be used with the field addition of a Belimo ZG R01 or equivalent 500 ohm resistor by others Refer to the wiring diagram for proper installa...

Page 56: ...unit nameplate CAUTION Use copper conductors only Use of aluminum conductors may result in equipment failure and overheating hazards All wiring in right hand compartment must be class 1 2 Wire leads...

Page 57: ...Air Temperature limit T6 freezestat across leaving air side of hydronic heating coil Cuts out below 38 F 2 F and automatically resets above 45 F 2 F Responds when any 15 of the capillary length senses...

Page 58: ...ls Making Control Connections For field provided control wiring connections refer to the appropriate control wiring schematic page 59 or page 60 Connect the field supplied controller to the harness pr...

Page 59: ...Fuse FB wire 56 furnished on 208 230 volt units only 4 T6 wires 550 551 furnished only on units with hot water or chilled water all others connect transformer wire to wire 501 6 Jumper wire A must be...

Page 60: ...sible to ensure controls operate correctly and protect the unit 3 Cap all unused transformer leads 4 X3 unused terminal 2 or 3 must be insulated 5 Fuse FB wire 56 57 furnished on 208 230 volt units on...

Page 61: ...ikinApplied com 61 IM 817 7 Controls by Others Field Installed CAUTION Refer to unit wiring diagram located on the right front panel for actual wiring Improper wiring can cause equipment and property...

Page 62: ...f unit power switch switch provided by Daikin The junction box has 1 25mm and 2 51mm knockouts located 10 1 2 267mm from right end of unit 3 Provide ground wire from grounding screw in switch junction...

Page 63: ...IM 817 7 Figure 122 Controls by Others Unit Power and Junction Box Connection Location Auto Transformer Fuses High Med Low Off Motor Speed Switch Switch Junction Box Terminal Strip Electric Power Wir...

Page 64: ...plied com Electric Heat Wiring Diagram Typical Figure 123 460 Volt 60 Hz 3 Phase CAUTION Refer to unit wiring diagram located on the right front panel for actual wiring Improper wiring can cause equip...

Page 65: ...80 55 100 70 130 80 150 230 60 1 Electric Heating Amperes 25 04 50 09 33 18 66 37 41 63 83 27 50 09 100 17 Unit Minimum Circuit Ampacity 34 40 65 71 44 58 86 06 55 14 107 19 65 71 128 32 Maximum Fuse...

Page 66: ...8 81 47 68 89 16 58 24 110 29 68 81 131 42 Maximum Fuse Size or Circuit Breaker Amps 40 70 50 90 60 120 70 140 265 60 1 Electric Heating Amperes 21 74 43 59 28 85 57 70 36 17 72 33 43 59 87 07 Unit Mi...

Page 67: ...40 of the total outside wall area 2 Single pane glass is used 3 Outside temperatures are below 35 F for a significant portion of the occupied period The need for window down draft protection will not...

Page 68: ...ns included with the Draftstop system for more detailed information Upper Channel or Backplate Assembly 1 Establish a level chalk line on the wall at a height specified for the top of the enclosure Se...

Page 69: ...7mm 4 102mm 1 25mm 277 8 708mm 18 457mm 4 102mm 1 25mm End View With 4 x 22 102mm x 559mm Cut out 277 8 708mm 22 559mm 4 102mm 1 25mm 277 8 708mm 22 559mm 4 102mm 1 25mm End View With 2 x 51 4 51mm x...

Page 70: ...p View 28 711mm 6 152mm End View With No Cut out 277 8 708mm Finned Radiation System Finned radiation down draft control is available for those who prefer it Made of furniture quality steel and design...

Page 71: ...tinnerman clips on unit subbase Screws insert through upper mounting holes inside unit end compartment and thread into tinnerman clips on end panel End Panel w Cut out Figure 132 Install End Panels W...

Page 72: ...emove debris dust dirt and any obstruction from the area in front of the return air intake grille at the floor as this will affect unit performance If a draftstop system has been installed be sure tha...

Page 73: ...omponents CAUTION Dirty or clogged filters can impact unit performance resulting in damage to the unit Figure 135 Filter installation 12 Left Front Access Panel Motor 12 Right Front Access Panel Top A...

Page 74: ..._______________________ Supply Voltage L1 L2___________ L2 L3___________ L3 L1____________ Rated _ _____________________________ Room Fan Motor Amps T1 ___________ RPM_ _________ Nameplate Rating _ __...

Page 75: ...ion system A Has all field piping been leak tested to 100 psig AVS AVV AVR AHF AHV AHR Yes No B Is expansion valve bulb properly installed and insulated Yes No C High pressure control cutout if applic...

Page 76: ...ndard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details Refer to Form 933 430285Y To find your local Daikin Applied...

Reviews: