SiUS341802E
Outline of Control (Indoor Unit)
Functions and Control
76
9.5
Drain Pump Control
9.5.1 Normal Operation
•
The float switch is ON in normal operation.
•
When cooling operation starts (thermostat ON), the drain pump turns ON simultaneously.
•
After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
•
The aim of residual operation after thermostat OFF is to eliminate the dew that condenses on
the indoor heat exchanger during cooling operation.
9.5.2 If the Float Switch is OFF with the Thermostat ON in Cooling Operation
•
When the float switch turns OFF, the thermostat turns OFF simultaneously.
•
After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
∗
1. If the float switch turns ON again during the residual operation of the drain pump, cooling
operation also turns on again (thermostat ON).
∗
2. If the float switch remains OFF even after the residual operation of the drain pump has ended,
the error code
A3
is displayed on the remote controller.
∗
3. The drain pump turns OFF once residual operation has ended, then turns ON again after 5
seconds.
∗
4. After
A3
is displayed and the unit comes to an abnormal stop, the thermostat will remain OFF
even if the float switch turns ON again.
Float switch
Error display
Thermostat
(running)
OFF
OFF
ON
ON
ON
OFF
Drain pump
ON
OFF
5 min.
OFF
OFF
ON
ON
ON
OFF
ON
OFF
5 min.
5 min. 5 sec.
5 sec.
Float switch
Error display
Thermostat
(running)
Drain pump
A3
}
∗
1
∗
2
∗
4
∗
3
Summary of Contents for Aurora Series
Page 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Page 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Page 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Page 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Page 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...