SiUS341802E
Troubleshooting by Error Code
Service Diagnosis
168
2.1.2 External Protection Device Abnormality (FXTQ-TA Only)
Error Code
A0-01
Applicable
Models
FXTQ-TA
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
When an open circuit occurs between external input terminals.
Supposed
Causes
Actuation of external protection device
Defective indoor unit PCB
Indoor unit fuse blown
Troubleshooting
Fuse (F1U)
is blown.
Ex
ternal
protection device
is connected to TB4 and
TB5 of the indoor unit
terminal.
The
external protection
device is opened.
Replace the indoor unit PCB.
Actuation of external protection
device.
Replace the fuse (F1U).
YES
YES
NO
NO
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.