background image

English

15

English

Trial Operation and Testing

1.

Trial operation and testing

• Trial operation should be carried out in either COOL or HEAT operation.

1-1. Measure the supply voltage and make sure that it is within the specified range.
1-2. In COOL operation, select the lowest programmable temperature; in HEAT operation, 

select the highest programmable temperature.

1-3. Carry out the trial operation in accordance with the operation manual to ensure that all

functions and parts, such as flap movement, are working properly.

• For protection, the system disables restart operation for 3 minutes after it is turned off.

1-4. After trial operation is complete, set the temperature to a normal level (26°C to 28°C in 

COOL operation, 20°C to 24°C in HEAT operation).

• When operating the air conditioner in COOL operation in winter, set it to the trial operation mode using the following 

method.

1) Press

and

at the same time.

2) Press

, select

, press

.

3) Press

or

to turn on the system.

• Trial operation will stop automatically after about 30 minutes.

To stop the operation, press

.

• Some of the functions cannot be used in the trial operation mode.

• The air conditioner draws a small amount of power in its standby mode. If the system is not to be used for some time after

installation, shut off the circuit breaker to eliminate unnecessary power consumption.

• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation mode 

when the circuit breaker is opened again.

2.

Test items 

Test items

Symptom

Check

Indoor and outdoor units are installed properly on solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating function

Refrigerant gas and liquid pipes and indoor drain hose extension are 
thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly earthed.

Electrical leakage

The specified wires are used for inter-unit wiring.

Inoperative or burn damage

Indoor or outdoor unit’s air inlet or air outlet are unobstructed

Incomplete cooling/heating function

Stop valves are opened.

Incomplete cooling/heating function

Indoor unit properly receives remote control commands.

No operation

3PEN482320-6B.book  Page 15  Wednesday, July 12, 2017  2:30 PM

Summary of Contents for ATXTP25K3V1B

Page 1: ...DITIONER INSTALLATION MANUAL R32 Split Series English Deutsch Fran ais Dansk Svenska Norsk Suomi Polski Models FTXTP25K3V1B FTXTP35K3V1B ATXTP25K3V1B ATXTP35K3V1B 3PEN482320 6B book Page 1 Wednesday J...

Page 2: ...B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo co...

Page 3: ...up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of t...

Page 4: ...inage and insulate piping to prevent condensation Improper drain piping may result in indoor water leakage and property damage Tighten the flare nut according to the specified method such as with a to...

Page 5: ...warm air is circulated throughout the room 7 the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote controller range 8 the unit is...

Page 6: ...under the centre of the front grille and while pushing up pull it toward you Installation method 1 Install the front grille and firmly engage the upper hooks 3 locations 2 Install 3 screws of the fro...

Page 7: ...l wiring cover as it was and pull the harness around as shown in the figure Removal method of metal plate electrical wiring covers 1 Remove the front grille 2 Remove the electrical wiring box 1 screw...

Page 8: ...or unit Push up the marked area at the lower part of the front grille to release the hooks If it is difficult to release remove the front grille 30mm or more from ceiling Front panel 50mm or more from...

Page 9: ...ll cover in the feed through hole to prevent possible heat electrical shock or fire Be sure to caulk the gaps around the pipes with caulking material to prevent water leakage 1 Bore a feed through hol...

Page 10: ...ce 2 After cutting off the pipe port cover perform filing Remove the burrs along the cut section using a half round needle file CAUTION If the pipe port cover is cut off using nippers the front grille...

Page 11: ...hose Replacing onto the left side 1 Remove the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drai...

Page 12: ...l it is firmly caught by the mounting plate hooks Secure indoor unit to the mounting plate with indoor unit fixing screws M4 12L 3 3 Wall embedded piping Follow the instructions given under left side...

Page 13: ..._A MR _B S U V W X A K R_ CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERIS...

Page 14: ...dded drain piping is required use appropriate parts that match the hose front end Figure of hose front end 4 When extending the drain hose use a commercially available extension hose with an inner dia...

Page 15: ...dryer to this R32 unit in order to guarantee its lifetime The drying material may dissolve and damage the system Protect or enclose the refrigerant tubing to avoid mechanical damage Incomplete flarin...

Page 16: ...10 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal...

Page 17: ...To stop the operation press Some of the functions cannot be used in the trial operation mode The air conditioner draws a small amount of power in its standby mode If the system is not to be used for...

Page 18: ...3PEN482320 6B book Page 1 Wednesday July 12 2017 2 30 PM...

Page 19: ...3PEN482320 6B book Page 2 Wednesday July 12 2017 2 30 PM...

Page 20: ...3P482320 6B 2017 06 Copyright 2017 Daikin 3PEN482320 6B book Page 1 Wednesday July 12 2017 2 30 PM...

Reviews: