background image

8 Finishing the indoor unit installation

Installation manual

13

ATXF20~42E5V1B
Daikin room air conditioner
3P650253-11H – 2022.10

3

Pass  the  interconnection  cable  from  the  outdoor  unit  through
the  feed-through  wall  hole,  through  the  back  of  the  indoor  unit
and through the front side.

Note: 

  In  case  the  interconnection  cable  was  stripped  in  advance,

cover the ends with insulating tape.

4

Bend the end of the cable up.

a
b

c

a

Terminal block

b

Electrical component block

c

Cable clamp

5

Strip the wire ends approximately 15 mm.

6

Match  wire  colours  with  terminal  numbers  on  the  indoor  unit
terminal blocks and firmly screw the wires to the corresponding
terminals.

7

Connect the earth wire to the corresponding terminal.

8

Firmly fix the wires with the terminal screws.

9

Pull  the  wires  to  make  sure  that  they  are  securely  attached,
then retain the wires with the wire retainer.

10

Shape  the  wires  so  that  the  service  cover  fits  securely,  then
close the service cover.

8

Finishing the indoor unit
installation

8.1

To insulate the drain piping,
refrigerant piping and
interconnection cable

1

After the drain piping, refrigerant piping and the electrical wiring
are finished. Wrap refrigerant piping, interconnection cable and
drain  hose  together  using  insulation  tape.  Overlap  at  least  half
the width of the tape with each turn.

d

e

c

b

f

a

a

Drain hose

b

Interconnection cable

c

Mounting plate (accessory)

d

Refrigerant piping

e

Indoor unit fixing screw M4×12L (accessory)

f

Bottom frame

8.2

To pass the pipes through the wall
hole

1

Shape the refrigerant pipes along the pipe path marking on the
mounting plate.

a

b

c

c

d

e

a

Drain hose

b

Caulk this hole with putty or caulking material

c

Adhesive vinyl tape

d

Insulation tape

e

Mounting plate (accessory)

NOTICE

▪ Do NOT bend refrigerant pipes.

▪ Do  NOT  push  the  refrigerant  pipes  onto  the  bottom

frame or the front grille.

2

Pass the drain hose and refrigerant piping through the wall hole
and seal the gap with a putty.

8.3

To fix the unit on the mounting
plate

1

Set  the  indoor  unit  on  the  mounting  plate  hooks.  Use  the  " "
marks as a guide.

2

Press the bottom frame of the unit with both hands to set it on
the  bottom  hooks  of  the  mounting  plate.  Make  sure  that  the
wires do NOT get squeezed anywhere.

Note: 

  Take  care  that  the  interconnection  cable  does  NOT  get

caught in the indoor unit.

3

Press the bottom edge of the indoor unit with both hands until it
is firmly caught by the mounting plate hooks.

4

Secure the indoor unit to the mounting plate using 2 indoor unit
fixing screws M4×12L (accessory).

Summary of Contents for ATXF35E

Page 1: ...on manual Daikin room air conditioner ATXF20E5V1B ATXF25E5V1B ATXF35E5V1B ATXF42E5V1B Questo manuale d istruzione fornito da trovaprezzi it Scopri tutte le offerte per Daikin ATXF35E o cerca il tuo pr...

Page 2: ...miniai bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo p...

Page 3: ...are used in accordance with our instructions as amended S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 S I 2008 1597 Supply of...

Page 4: ...run 15 10 2 1 To perform a test run in winter season 15 11 Disposal 15 12 Technical data 16 12 1 Wiring diagram 16 12 1 1 Unified wiring diagram legend 16 1 About the documentation 1 1 About this docu...

Page 5: ...sucked in This will cause abnormal pressure in the refrigeration cycle which may result in equipment damage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use f...

Page 6: ...them with bare hands DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacitors or electrical components befo...

Page 7: ...n and with applicable legislation and are executed ONLY by authorised persons 5 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Air flow...

Page 8: ...and firmly engage the 3 upper hooks 2 Install 2 screws back on the front grille 3 Install the air filter and then mount the front panel 5 2 5 To remove the electrical wiring box cover 1 Remove the fr...

Page 9: ...t cover INFORMATION To connect the piping on right side right bottom left side or left bottom the pipe port cover MUST be removed 1 Cut off the pipe port cover from inside the front grille using a cop...

Page 10: ...t side and install it on the left side 1 Remove the insulation fixing screw on the right side and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side NOTICE...

Page 11: ...e a spanner and torque wrench together to tighten the flare nut when connecting the piping This to prevent nut cracking and leaks a b c d a Torque wrench b Spanner c Piping union d Flare nut Piping si...

Page 12: ...thout thermal insulation as such pipes will be very hot 7 1 Specifications of standard wiring components NOTICE We recommend using solid single core wires If stranded wires are used twist the conducto...

Page 13: ...rap refrigerant piping interconnection cable and drain hose together using insulation tape Overlap at least half the width of the tape with each turn d e c b f a 2 a Drain hose b Interconnection cable...

Page 14: ...he operation lamp was blinking repeat the setting process from the beginning 9 When the setting is complete press Model Button FTXF ATXF Result The user interface will return to the previous screen 10...

Page 15: ...ary 2 When the test run is finished set the temperature to a normal level In cooling mode 26 28 C in heating mode 20 24 C 3 The system stops operating 3 minutes after the unit is turned OFF 10 2 1 To...

Page 16: ...Meaning A P Printed circuit board BS Pushbutton ON OFF operation switch BZ H O Buzzer C Capacitor AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ NE Connection connector D V D Diode DB Diode brid...

Page 17: ...3P650253 11H 2022 10 Symbol Meaning V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion va...

Page 18: ......

Page 19: ......

Page 20: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P650253 11H 2022 10 Copyright 2...

Reviews: