2 Specific installer safety instructions

Installation manual

5

RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 split series
3P482320-14U – 2021.03

Unit installation (see 

"4 Unit installation"

 [

4

 7])

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

Installation site (see 

"4.1 Preparing the installation site"

 [

4

 7])

CAUTION

▪ Check  if  the  installation  location  can  support  the  unit's

weight. Poor installation is hazardous. It can also cause
vibrations or unusual operating noise.

▪ Provide sufficient service space.

▪ Do  NOT  install  the  unit  so  that  it  is  in  contact  with  a

ceiling or a wall, as this may cause vibrations.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (e.g.  open  flames,  an  operating
gas  appliance,  or  an  operating  electric  heater).  The  room
size shall be as specified in the General safety precaution.

Connecting the refrigerant piping (see 

"5.2 Connecting the

refrigerant piping"

 [

4

 9])

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

CAUTION

▪ No  brazing  or  welding  on  site  for  units  with  R32

refrigerant charge during shipment.

▪ During installation of the refrigeration system, joining of

parts with at least one part charged shall be performed
taking  into  account  the  following  requirements:  inside
occupied spaces non permanent joints are not allowed
for  R32  refrigerant  except  for  site  made  joints  directly
connecting  the  indoor  unit  to  piping.  Site  made  joints
directly connecting piping to indoor units shall be of non
permanent type.

CAUTION

▪ Use the flare nut fixed to the unit.

▪ To  prevent  gas  leakage,  apply  refrigeration  oil  only  to

the inside of the flare. Use refrigeration oil for R32.

▪ Do NOT reuse joints.

CAUTION

▪ Do NOT use mineral oil on flared part.

▪ Do NOT reuse piping from previous installations.

▪ NEVER  install  a  drier  to  this  R32  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

WARNING

Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is NOT connected and
the stop valve is open when the compressor is run, air will
be  sucked  in.  This  will  cause  abnormal  pressure  in  the
refrigeration cycle, which may result in equipment damage
and even injury.

CAUTION

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

CAUTION

Do  NOT  open  the  valves  before  flaring  is  complete.  This
would cause refrigerant gas leakage.

DANGER: RISK OF EXPLOSION

Do NOT start the unit if it is vacuumed.

Charging refrigerant (see 

"6 Charging refrigerant"

 [

4

 10])

WARNING

The  refrigerant  inside  the  unit  is  mildly  flammable,  but
normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater, or a cooker, this may result in fire, or the formation
of a harmful gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room,  and  contact  the  dealer  where  you  purchased  the
unit.

Do  NOT  use  the  unit  until  a  service  person  confirms  that
the  part  from  which  the  refrigerant  leaked  has  been
repaired.

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  ALWAYS  use  protective

gloves and safety glasses.

CAUTION

To  avoid  compressor  breakdown,  do  NOT  charge  more
than the specified amount of refrigerant.

WARNING

NEVER  directly  touch  any  accidental  leaking  refrigerant.
This could result in severe wounds caused by frostbite.

Electrical installation (see 

"7 Electrical installation"

 [

4

 11])

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

Summary of Contents for ARXTP25R2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXTA30B2V1B RXTM30R2V1B RXTM40R2V1B RXTP25R2V1B RXTP35R2V1B ARXTP25R2V1B ARXTP35R2V1B ...

Page 2: ...vejä sellaisina kuin ne ovat muutettuina v platném znění Smjernice kako je izmijenjeno irányelv ek és módosításaik rendelkezéseit z późniejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Директиви с техните изменения Direktyvose su papildymais Direktīvās un to papildinājumos Smernice v platnom znení Değiş...

Page 3: ...in sallittu lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpovíd...

Page 4: ...14 13 1 1 Unified wiring diagram legend 14 13 2 Piping diagram 16 13 2 1 Piping diagram Outdoor unit 16 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask him her to keep it for future reference Target audience Authorised installers WARNING Make sure installation servicing maintenance repair and applied materials follow the i...

Page 5: ...nstallations NEVER install a drier to this R32 unit to guarantee its lifetime The drying material may dissolve and damage the system WARNING Connect the refrigerant piping securely before running the compressor If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run air will be sucked in This will cause abnormal pressure in the refrigeration cycle which may...

Page 6: ...asure the voltage at the terminals of main circuit capacitors or electrical components before servicing The voltage MUST be less than 50 V DC before you can touch electrical components For the location of the terminals see the wiring diagram Finishing indoor unit installation see 8 Finishing the outdoor unit installation 412 DANGER RISK OF ELECTROCUTION Make sure that the system is earthed properl...

Page 7: ...terials and installation shall comply with the applicable legislation In Europe EN378 is the applicable standard 4 1 Preparing the installation site WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continuously operating ignition sources e g open flames an operating gas appliance or an operating electric heater The room size shall be as...

Page 8: ...snowfall areas it is very important to select an installation site where the snow will NOT affect the unit If lateral snowfall is possible make sure that the heat exchanger coil is NOT affected by the snow If necessary install a snow cover or shed and a pedestal 4 2 Mounting the outdoor unit 4 2 1 To provide the installation structure Use a vibration proof rubber field supply in cases where vibrat...

Page 9: ...ipe length 1 5 m Maximum allowable height difference 15 m 5 2 Connecting the refrigerant piping DANGER RISK OF BURNING SCALDING CAUTION No brazing or welding on site for units with R32 refrigerant charge during shipment During installation of the refrigeration system joining of parts with at least one part charged shall be performed taking into account the following requirements inside occupied sp...

Page 10: ...s after installing the refrigerant piping and performing vacuum drying Running the system with the stop valves closed may break the compressor 6 Charging refrigerant 6 1 About the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gases into the atmosphere Refrigerant type R32 Global warming potential GWP value 675 WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside th...

Page 11: ...t Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Use the GWP value mentioned on the refrigerant charge label 2 Fix the label on the inside of the outdoor unit near the gas and liquid stop valves 7 Electrical installation DANGER RISK OF ELECTROCUTION WARNING All wiring MUST be performed by an authorised electrician and MUS...

Page 12: ...20 240 V c d f a b e a Interconnection cable b Power supply cable c Circuit breaker d Residual current device e Power supply f Earth 3 4 Tighten the terminal screws securely We recommend using a Phillips screwdriver 8 Finishing the outdoor unit installation 8 1 To finish the outdoor unit installation DANGER RISK OF ELECTROCUTION Make sure that the system is earthed properly Turn off the power supp...

Page 13: ...insulated The stop valves gas and liquid on the outdoor unit are fully open Drainage Make sure drainage flows smoothly Possible consequence Condensate water might drip The indoor unit receives the signals of the user interface The specified wires are used for the interconnection cable The fuses circuit breakers or locally installed protection devices are installed according to this document and ha...

Page 14: ... numbers in ascending order for each part and is represented in the overview below by in the part code Symbol Meaning Symbol Meaning Circuit breaker Protective earth Connection Protective earth screw Connector A Rectifier Earth Relay connector Field wiring Short circuit connector Symbol Meaning Symbol Meaning Fuse Terminal INDOOR Indoor unit Terminal strip OUTDOOR Outdoor unit Wire clamp Residual ...

Page 15: ...eak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge Insulated gate bipolar transistor IGBT power modu...

Page 16: ... 7 9 CuT 9 5 CuT 9 5 CuT 12 7 CuT 9 5 CuT 9 5 CuT 9 5 CuT 6x7 0 CuT HPS 6 4 CuT k 12 7 CuT 6x3 2 CuT 6 4 CuT f h i j e a Field piping liquid l Accumulator b Field piping gas m Muffler c Liquid stop valve n ON heating 4 way valve d Gas stop valve o Discharge pipe thermistor e Filter p Outdoor air temperature thermistor f Electronic expansion valve q Compressor g Muffler with filter r Propeller fan ...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P482320 14U 2021 03 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...

Reviews: