11

English

Wiring

 WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating,

electrical shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the

terminal block.) Doing so may cause electric shock or fire.

• Be sure to install an earth leak detector. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that an earth leak detector capable of handling higher harmonics must be used, in
order to prevent malfunctioning of the earth leak detector itself.)

• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.Do not turn ON the safety breaker

until all work is completed.

1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between the

indoor and outdoor units so that the terminal
numbers match. Tighten the terminal screws
securely. We recommend a flathead
screwdriver be used to tighten the screws.
The screws are packed with the terminal block.

Observe the notes mentioned below when wiring to the power supply terminal block.
Precautions to be taken for power supply wiring.

 CAUTION

• When connecting the connection wires to the terminal block using a single core wire, be sure to perform curling.

Problems with the work may cause heat and fires.

• If the stranded wires must be used, make sure to use the round

crimp-style terminal for connection to the power supply terminal
block. Place the round crimp-style terminals on the wires up to the
covered part and secure in place.

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.

Safety 
breaker 
16A

Earth leakage 
circuit breaker

Earth

Inter-unit wire 
4-core 1.5mm² or more
H05RN

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power supply
50Hz 220-240V

Firmly fix the wires with 
the terminal screws.

Power supply wire 
3-core 2.5mm² or more
H05RN

Use the specified wire type 
and connect it securely.

Firmly secure wire retainer so wire 
terminations will not receive external stress.

Power supply 
terminal block

Shape wires so 
that the service lid 
and stop valve 
cover fit securely.

Strip wire end 
to this point.

Excessive strip length 
may cause electrical 
shock or leakage.

Good

Wrong

Good

Wrong

Stripping wire at terminal block

Stranded wire

Round crimp-style 
terminal

3PEN386697-4L.book  Page 11  Monday, July 31, 2017  2:37 PM

Summary of Contents for ARXTP25N2V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models RXTM30N2V1B RXTM40N2V1B RXTP25N2V1B RXTP35N2V1B ARXTP25N2V1B ARXTP35N2V1B 3PEN386697 4L book Page 1 Monday July 31 2017 2 37 PM КОНДИЦИОНЕРЫ DAIKIN ...

Page 2: ...ifikat G Risikoklasse H Se også næste side 11 enligt A och godkänts av B enligt Certifikatet C i enlighet med den Tekniska Konstruktionsfilen D som positivt intygats av E Fastsatt modul F vilket också framgår av Certifikat G Riskkategori H Se även nästa sida 12 som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gj...

Page 3: ...аксимално допустима температура TS TSmin Минимална температура от страната на ниското налягане L C TSmax Температура на насищане съответстваща на максимално допустимото налягане PS M C Охладител N Настройка на предпазното устройство за налягане P bar Фабричен номер и година на производство вижте табелката на модела 22 Maksimalus leistinas slėgis PS K bar Minimali maksimali leistina temperatūra TS ...

Page 4: ... the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or securing of wires may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result...

Page 5: ...emperature of refrigerant circuit will be high please keep the inter unit wire away from copper pipes that are not thermally insulated This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay persons Provide a logbook and machine card In accordance with the applicable legislation it may be necessary to provi...

Page 6: ...d radio sets This is to prevent interference to images and sounds Noises may be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture...

Page 7: ...se foot bolts or wires 250mm from wall unit mm How to remove the stop valve cover Remove the screw on the stop valve cover Slide the cover downward to remove it How to attach the stop valve cover Insert the upper part of the stop valve cover into the outdoor unit Tighten the screws Stop valve cover Allow space for piping and electrical servicing Be sure to add the proper amount of additional refri...

Page 8: ...fter installed In accordance with the foundation drawing fix the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface More than 50 Direction of air 1200 or less More than 100 More than 50 More than 50 More t...

Page 9: ...r surface of the flare Use refrigeration oil for R32 Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage After the piping work is finished after checking for gas leaks open the stop valves or the compressor might break down Ensure that the field piping and connections are not subjected to stress Align the centres of both flares and tighten the fla...

Page 10: ...ion cycle When refrigerant gas leaks occur ventilate the room as soon and as much as possible R32 as well as other refrigerants should always be recovered and never be released directly into the environment Use a vacuum pump for R32 exclusively Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit Use tools for R32 such as the gauge manifold charging hose or ...

Page 11: ... 1000 GWP kg kg kg GWP 675 675 R32 R32 NOTE National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit Sticking instructions are illustrated on the backside of that label NOTICE In Europe the greenhouse...

Page 12: ... set the operation mode to cooling CAUTION When pressing the switch do not touch the terminal block It has a high voltage so doing so may cause electric shock After closing the liquid stop valve close the gas stop valve within 3 minutes then stop the forced cooling operation Liquid stop valve Gas stop valve Service port Valve cap Close Hexagonal wrench WARNING The unit is accompanied with the labe...

Page 13: ...oor unit is installed where the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might cause dew condensation fro...

Page 14: ...mentioned below when wiring to the power supply terminal block Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal block using a single core wire be sure to perform curling Problems with the work may cause heat and fires If the stranded wires must be used make sure to use the round crimp style terminal for connection to the power supply term...

Page 15: ... T THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT LAMP LIGHT EMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHT EMITTINGDIODE SERVICEMONITOR GREEN S PH HPS PRESSURESWITCH HIGH HIGH VOLTAGE HIGH VOLTAGE S PL PRESSURESWITCH LOW IES INTELLIGENT ...

Page 16: ...its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test items Test items Symptom Check Indoor and outdoor units are installed pr...

Page 17: ...piping Discharge pipe thermistor Propeller fan Heating Cooling Refrigerant flow ON heating Muffler with filter Muffler Muffler 6x7 0 CuT 7 9 CuT 6 4 CuT 6 4 CuT 9 5 CuT 7 9 CuT 9 5 CuT 9 5 CuT 12 7 CuT 9 5 CuT 9 5 CuT 9 5 CuT 6x7 0 CuT HPS High pressure switch Automatic reset 6 4 CuT Heat exchanger thermistor 12 7 CuT 6x3 2 CuT 6 4 CuT Electronic expansion valve Muffler Distributor Capillary tube ...

Page 18: ...3PEN386697 4L book Page 1 Monday July 31 2017 2 37 PM ...

Page 19: ...3PEN386697 4L book Page 2 Monday July 31 2017 2 37 PM ...

Page 20: ...3P386697 4L 2017 06 Copyright 2017 Daikin 3PEN386697 4L book Page 1 Monday July 31 2017 2 37 PM ...

Reviews: