SiBE04-809
Troubleshooting
Service Diagnosis
77
4.
Troubleshooting
4.1
Error Codes and Description
★
: Displayed only when system-down occurs.
Code Indication Description
Reference
Page
System
00
Normal
—
U0
★
Insufficient gas
U2
Low-voltage detection or over-voltage detection
U4
Signal transmission error (between indoor and outdoor units)
U5
Signal transmission error (between indoor unit and wired remote
controller)
UA
Unspecified voltage (between indoor and outdoor unit)
Indoor
Unit
A1
Indoor unit PCB abnormality
A5
Freeze-up protection control or high pressure control
A6
Fan motor or related abnormality
C4
Heat exchanger temperature thermistor abnormality
C7
Front panel open/close fault
C9
Room temperature thermistor abnormality
Outdoor
Unit
E1
Outdoor unit PCB abnormality
E5
★
OL activation (compressor overload)
E6
★
Compressor lock
E7
DC fan lock
E8
Input over current detection
EA
Four way valve abnormality
F3
Discharge pipe temperature control
F6
High pressure control in cooling
H0
Compressor system sensor abnormality
H6
Position sensor abnormality
H8
DC voltage/current sensor abnormality
H9
Outdoor air thermistor or related abnormality
J3
Discharge pipe temperature thermistor or related abnormality
J6
Heat exchanger temperature thermistor or related abnormality
L3
Electrical box temperature rise
L4
Radiation fin temperature rise
L5
Output over current detection
P4
Heat radiation fin thermistor or related abnormality
U7
Signal transmission error on outdoor unit PCB
Summary of Contents for ARXG25E3V1B
Page 1: ...SiBE04 809 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series ...
Page 11: ...Introduction SiBE04 809 x ...
Page 12: ...SiBE04 809 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 14: ...SiBE04 809 Specifications 3 Part 2 Specifications 1 Specifications 4 ...