SiBE04-809
Troubleshooting
Service Diagnosis
95
4.16
Discharge Pipe Temperature Control
Remote
Controller
Display
F3
Method of
Malfunction
Detection
The discharge pipe temperature control (stop, frequency drooping, etc.) is checked with the
temperature being detected by the discharge pipe thermistor.
Malfunction
Decision
Conditions
If a stop takes place 4 times successively due to abnormal discharge pipe temperature, the
system will be shut down.
If the temperature being detected by the discharge pipe thermistor rises above
°C, the
compressor will stop. (The error is cleared when the temperature has dropped below
°C.)
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Supposed
Causes
Refrigerant shortage
Four way valve malfunctioning
Discharge pipe thermistor defective
(heat exchanger or outdoor temperature thermistor defective)
Outdoor unit PCB defective
Water mixed in the local piping
Electronic expansion valve defective
Stop valve defective
Stop temperatures
(1) above 45Hz (rising), above 40Hz (dropping)
110
97
(2) 30~45Hz (rising), 25~40Hz (dropping)
105
92
(3) below 30Hz (rising), below 25Hz (dropping)
99
86
Summary of Contents for ARXG25E3V1B
Page 1: ...SiBE04 809 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series ...
Page 11: ...Introduction SiBE04 809 x ...
Page 12: ...SiBE04 809 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 14: ...SiBE04 809 Specifications 3 Part 2 Specifications 1 Specifications 4 ...