8
|
Charging refrigerant
Installer reference guide
47
ARXM50-71+RXM42~7 RXP50~7 RXA42+5
RXF50+6 RXF7 RXJ5 ARXF50~71A2V1B
R32 split series
4P513661-9J – 2020.05
8.3 Precautions when charging refrigerant
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
"2 General safety precautions"
▪
"7.1 Preparing refrigerant piping"
8.4 To determine the additional refrigerant amount
For ARXM71R
If the total liquid piping
length is…
Then…
≤10 m
Do NOT add additional refrigerant.
>10 m
R=(total length (m) of liquid piping–10 m)×0.035
R=Additional charge (kg) (rounded in units of
0.01 kg)
For other outdoor units
If the total liquid piping
length is…
Then…
≤10 m
Do NOT add additional refrigerant.
>10 m
R=(total length (m) of liquid piping–10 m)×0.020
R=Additional charge (kg) (rounded in units of
0.01 kg)
INFORMATION
Piping length is the one-way length of liquid piping.
8.5 To determine the complete recharge amount
INFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory
refrigerant charge (see unit name plate) + the determined additional amount.
8.6 To charge additional refrigerant
WARNING
▪
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
▪
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
▪
When charging refrigerant, ALWAYS use protective gloves and safety glasses.