IM 1083-3
28 www.DaikinApplied.com
Table 10: Wiring Diagram Legend for
Figure 43 on page 26 and Figure 44 on page 27
Symbol Description
Symbol Description
Symbol Description
A1
Actuator- Outdoor Air
HP
High Pressure Switch
R32
Relay - Drain Pan Heater
A2
Actuator- Face & Bypass
ICT
Sensor - Indoor DX Coil Temperature
R28
Relay - Outdoor Motor Air
CP1
Motor Compressor 2-Stage
IH
Sensor - Indoor Humidity
RV
Reversing Valve
C1
Compressor Contactor
MCB
Main Control Board
RAT
Sensor - Room Air Temperature
CAP1
Capacitor Run
NTWK
Network Connection
T6
Thermostat - Freeze Stat
CEH1-3
Electric Heat Contactor
OAT
Sensor - Outdoor Air Temperature
TB1
Terminal Block - 24VAC+
CO2
Sensor - Indoor Air CO2
OCT
Sensor - Outdoor DX Coil Temperature
TB2
Terminal Block – 24VAC Gnd
DAT
Sensor - Discharge Air Temperature
OH
Sensor - Outdoor Humidity
TB3
(A, B) Terminal Block – Main Power
DCS
Switch - Unit Power
OH1
Thermostat - Overheat
TBE
Terminal Block - Electric Heat
DF
Dead Front Switch
OH2
Thermostat - Overheat
TR1
Transformer - Motor Speed
EH1-6
Heater - Electric
OHM
E.H. Man Reset - Overheat Stat
TR3
Transformer - 208 / 230V-24V, 75VA
EH10
Heater - Outdoor Drain Pan
PL1
LED Occupancy / Fault Status
TR4
Transformer - 460V–230V
F1A/F1B
Fuse - Compressor
R1-R3
Relay Electric Heat (Backup)
TR5
Transformer - 208 / 230V-24V
F2A/F3C
Fuse - Electric Heat
R10-R12
Relay – Electric Heat
V1
Valve - Heat EOC (Accessory)
FA/FB
Fuse– Control, Load
R4H
Relay – Fan High Speed
V2
Valve - Cool EOC (Accessory)
FC/FD
Fuse– Control, Transformer
R4M
Relay– Fan Medium Speed
VH
Valve - Heat (Accessory)
FMI
Motor - Room Fan
R4L
Relay– Fan Low Speed
VC
Valve - Cool (Accessory)
FMO
Motor Outdoor Air
Notes:
1. All electrical installation must be in accordance with national and local electrical codes and job wiring schematic.
External wiring options - see IM for the different configured options, wiring to be minimum 18 gauge, 90°C.
3. EC motors are factory programmed for specified air flow. Contact Daikin Applied for replacement.
4. Cap extra wire. Switch wire 42A to red wire for 208V operation.
5. Switch wire 509 to terminal 2 for 208V operation.
6. Devices in legend may or may not be on unit.
Electrical Data
ARQ & GRQ – Size 024
Volt/Hz/Phase
Voltage Range
Room Fan
FLA
Compressor
Heating Option
Power Supply
Min.
Max.
RLA
LRA
Heat Type
Heater
Kw
Rated
Heater
Amps
MCA
Maximum
Fuse
208/60/1
197
228
2.7
11.7
58.3
None
–
–
17.3
25
2.7
11.7
58.3
Elec. Heat1
Low (3 elem.)
8.0
38.5
65.4
70
2.7
11.7
58.3
High (6 elem.)
16.0
76.9
113.5
125
230/60/1
207
253
2.7
11.7
58.3
None
–
–
17.3
25
2.7
11.7
58.3
Elec. Heat1
Low (3 elem.)
7.3
33.3
59.0
60
2.7
11.7
58.3
High (6 elem.)
14.7
66.7
100.7
110
208/60/3
197
228
2.7
6.5
55.4
None
–
–
10.8
15
2.7
6.5
55.4
Elec. Heat1
Low (3 elem.)
8.0
22.2
38.6
40
2.7
6.5
55.4
High (6 elem.)
16.0
44.4
66.3
70
230/60/3
207
253
2.7
6.5
55.4
None
–
–
10.8
15
2.7
6.5
55.4
Elec. Heat1
Low (3 elem.)
7.3
19.2
34.9
35
2.7
6.5
55.4
High (6 elem.)
14.7
38.5
58.9
60
460/60/3
414
506
2.7
3.5
28.0
None
–
–
7.1
15
2.7
3.5
28.0
Elec. Heat1
Low (3 elem.)
7.3
9.6
19.1
20
2.7
3.5
28.0
High (6 elem.)
14.7
19.2
31.1
35
1
Electric Heat Options are without Compressor and Outdoor Fan.