Daikin Trouble Shooting Guide
Past & Current Models
Daikin Fault Codes
Indoor Fault Codes
Fault Code Definition
Supposed Causes
Split
Skyair
VRV
Package
A0
External protection active
External protection wired to T1-T2 active
•
•
•
A1
Failure of indoor PCB
Defect of PCB or noise
•
•
•
•
A3
High water level
Float switch open circuit
•
•
•
A5
HP control in heating or freeze
protection in cooling
Poor airflow, short circuit, EEV, refrigerant charge,
indoor coil sensor incorrect value
•
A6
Fan motor failure
Locked, over current, over load
•
•
•
•
A7
Failure of louvre motor
Louvre motor/indoor PCB failed
•
•
A8
Failure of power supply
Over current of AC input, defect of supply
•
•
A9
EEV failure
Defect of EEV motor, indoor PCB
•
•
AF
High water level
Float switch open circuit while thermo off
•
•
AH
Failure of dust collector
Defect of dust collecting element, PCB
•
•
•
AJ
Capacity setting error
Capacity setting adaptor missing
•
•
•
C1
Communication failure. Between
main-sub PCB
Failure of communication fan motor
control driver
•
•
C4
Indoor coil sensor
Open/short circuit
•
•
•
•
C5
Suction pipe sensor
Open/short circuit
•
•
•
C6
Failure of fan motor driver
Defect of fan motor sensor, control driver
•
•
C7
Front panel driving motor fault
Defect of limit switch, front panel driving motor
•
C9
Return air sensor fault
Return air sensor open/short circuit
•
•
•
•
CA
Discharge air sensor fault
Discharge air sensor open/short circuit
•
•
CC
Failure of humidity sensor
Failed humidity sensor
•
•
CJ
Failure of remote sensor
Defect of remote controller sensor
•
•
Daikin Fault Codes
Outdoor Fault Codes
Fault Code Definition
Supposed Causes
Split
Skyair
VRV
Package
E0
Protection devices tripped
Outdoor safety device tripped
•
•
•
E1
Failure of outdoor PCB
Defect of PCB or noise
•
•
•
•
E3
High pressure
High pressure switch tripped
•
•
•
E4
Low pressure
Low pressure switch tripped
•
•
•
E5
Inverter compressor lock
Inverter compressor locked
•
•
•
E5
Inverter compressor to hot
Compressor windings too hot
•
E6
DOL compressor locked
High current draw
•
•
•
•
E7
Fan motor failure
Failed fan motor, PCB
•
•
•
•
E8
Inv compressor high current
Compressor, PCB
•
•
•
E9
EEV motor failure
EEV motor, PCB
•
•
•
EA
4-way valve failure
Defect of valve, PCB, sensor
•
EC
Inlet water temperature
Abnormal water temperature
•
EF
Thermal storage unit defect
Thermal storage EEV, PCB, sensor
•
F3
High discharge temperature
Discharge temperature over 110°C
•
•
•
•
F6
High pressure in cooling
Detected by outdoor coil sensor
•
F6
Over charged
Refrigerant over charge
•
•
H0
Compressor sensor system
All sensors disconnected
•
H1
Failure of humidifier damper
Defect of limit switch/damper
•
H3
Failure of hp switch
High pressure switch open circuit
•
•
•
•
H4
Failure of lp switch
Low pressure switch open circuit
•
•
H5
Failure of compressor sensor
Defect of compressor overload sensor
•
H6
Compressor position failure
Position detection error
•
H7
Failure of fan motor signal
Defect of fan motor, PCB
•
•
•
H8
Compressor input error
Defect of transistor, PCB, reactor
•
H9
Failed ambient sensor
Sensor open short circuit
•
•
•
•
J1
Failed pressure sensor
Pressure sensor failed
•
•
J2
Failed current sensor
Defect of current sensor, PCB, compressor
•
•
•
J3
Failed discharge pipe sensor
Discharge pipe sensor open/short circuit
•
•
•
•
J4
Failed outdoor coil vapour sensor
Sensor open/short circuit
•
•
J5
Failed suction pipe sensor
Sensor open/short circuit
•
•
•
•
J6
Failed outdoor coil sensor
Sensor open/short circuit
•
•
•
•
J7
Failed liquid pipe sensor
Sensor open/short circuit
•
•
•
J8
Failed liquid pipe sensor
Sensor open/short circuit
•
J9
Failed sub cool heat exchanger sensor Sensor open/short circuit
•
•
•
•
JA
Failed high pressure sensor
High pressure sensor open/short circuit
•
•
•
JC
Failed low pressure sensor
Low pressure sensor open/short circuit
•
•
•
JH
Failed oil temperature sensor
Open/short circuit
•