Daikin Trouble Shooting Guide

Past & Current Models

Daikin Fault Codes

Indoor Fault Codes
Fault Code Definition

Supposed Causes

Split

Skyair

VRV

Package

A0

External protection active

External protection wired to T1-T2 active

A1

Failure of indoor PCB

Defect of PCB or noise

A3

High water level

Float switch open circuit

A5

HP control in heating or freeze  

protection in cooling 

Poor airflow, short circuit, EEV, refrigerant charge, 

indoor coil sensor incorrect value

A6

Fan motor failure

Locked, over current, over load

A7

Failure of louvre motor

Louvre motor/indoor PCB failed

A8

Failure of power supply

Over current of AC input, defect of supply

A9

EEV failure

Defect of EEV motor, indoor PCB

AF

High water level

Float switch open circuit while thermo off

AH

Failure of dust collector

Defect of dust collecting element, PCB

AJ

Capacity setting error

Capacity setting adaptor missing

C1

Communication failure. Between 

main-sub PCB

Failure of communication fan motor  

control driver

C4

Indoor coil sensor

Open/short circuit

C5

Suction pipe sensor

Open/short circuit

C6

Failure of fan motor driver

Defect of fan motor sensor, control driver

C7

Front panel driving motor fault

Defect of limit switch, front panel driving motor

C9

Return air sensor fault

Return air sensor open/short circuit

CA

Discharge air sensor fault

Discharge air sensor open/short circuit

CC

Failure of humidity sensor

Failed humidity sensor

CJ

Failure of remote sensor

Defect of remote controller sensor

Daikin Fault Codes

Outdoor Fault Codes
Fault Code Definition

Supposed Causes

Split

Skyair

VRV

Package

E0

Protection devices tripped

Outdoor safety device tripped

E1

Failure of outdoor PCB

Defect of PCB or noise

E3

High pressure

High pressure switch tripped

E4

Low pressure

Low pressure switch tripped

E5

Inverter compressor lock

Inverter compressor locked

E5

Inverter compressor to hot

Compressor windings too hot

E6

DOL compressor locked

High current draw

E7

Fan motor failure

Failed fan motor, PCB

E8

Inv compressor high current

Compressor, PCB

E9

EEV motor failure

EEV motor, PCB

EA

4-way valve failure

Defect of valve, PCB, sensor

EC

Inlet water temperature

Abnormal water temperature

EF

Thermal storage unit defect

Thermal storage EEV, PCB, sensor

F3

High discharge temperature

Discharge temperature over 110°C

F6

High pressure in cooling

Detected by outdoor coil sensor

F6

Over charged

Refrigerant over charge

H0

Compressor sensor system

All sensors disconnected

H1

Failure of humidifier damper

Defect of limit switch/damper

H3

Failure of hp switch

High pressure switch open circuit

H4

Failure of lp switch

Low pressure switch open circuit

H5

Failure of compressor sensor 

Defect of compressor overload sensor 

H6

Compressor position failure

Position detection error

H7

Failure of fan motor signal

Defect of fan motor, PCB

H8

Compressor input error

Defect of transistor, PCB, reactor

H9

Failed ambient sensor 

Sensor open short circuit

J1

Failed pressure sensor

Pressure sensor failed

J2

Failed current sensor

Defect of current sensor, PCB, compressor

J3

Failed discharge pipe sensor

Discharge pipe sensor open/short circuit

J4

Failed outdoor coil vapour sensor

Sensor open/short circuit

J5

Failed suction pipe sensor

Sensor open/short circuit

J6

Failed outdoor coil sensor

Sensor open/short circuit

J7

Failed liquid pipe sensor

Sensor open/short circuit

J8

Failed liquid pipe sensor

Sensor open/short circuit

J9

Failed sub cool heat exchanger sensor Sensor open/short circuit

JA

Failed high pressure sensor

High pressure sensor open/short circuit

JC

Failed low pressure sensor

Low pressure sensor open/short circuit

JH

Failed oil temperature sensor

Open/short circuit