![Daikin Altherma M EDLQ011-016CW1 Installer'S Reference Manual Download Page 58](http://html1.mh-extra.com/html/daikin/altherma-m-edlq011-016cw1/altherma-m-edlq011-016cw1_installers-reference-manual_4143467058.webp)
8 Configuration
Installer reference guide
58
EBLQ+EDLQ011~W1 + EK(2)CB
EKMB9W1
Daikin Altherma low temperature monobloc
4P522034-1 – 2018.01
#
Code
Description
[7.7.1.1]
[1-00]
[1-01]
[1-02]
[1-03]
<< continuation
▪ [1-00]:
Low
outdoor
ambient
temperature. –40°C~+5°C (default: –
10°C)
▪ [1-01]:
High
outdoor
ambient
temperature. 10°C~25°C (default:
15°C)
▪ [1-02]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or drops below
the
low
ambient
temperature.
[9‑01]°C~[9‑00]°C (default: 45°C).
Note:
This value should be higher
than [1-03] as for low outdoor
temperatures
warmer
water
is
required.
▪ [1-03]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or rises above
the
high
ambient
temperature.
[9‑01]°C~min(45, [9‑00])°C (default:
35°C).
Note:
This value should be lower
than [1-02] as for high outdoor
temperatures less warm water is
required.
#
Code
Description
[7.7.1.2]
[1-06]
[1-07]
[1-08]
[1-09]
Set weather-dependent cooling:
[1-09]
[1-08]
Ta
Tt
[1-06]
[1-07]
▪ T
t
: Target leaving water temperature
(main)
▪ T
a
: Outdoor temperature
continued >>
#
Code
Description
[7.7.1.2]
[1-06]
[1-07]
[1-08]
[1-09]
<< continuation
▪ [1-06]:
Low
outdoor
ambient
temperature. 10°C~25°C (default:
20°C)
▪ [1-07]:
High
outdoor
ambient
temperature. 25°C~43°C (default:
35°C)
▪ [1-08]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or drops below
the low ambient temperature.
Between minimum and maximum
leaving
water
temperature
[9‑03]°C~[9‑02]°C (default: 22°C).
Note:
This value should be higher
than [1-09] as for low outdoor
temperatures
less
cold
water
suffices.
▪ [1-09]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or rises above
the high ambient temperature.
Between minimum and maximum
leaving
water
temperature
[9‑03]°C~[9‑02]°C (default: 18°C).
Note:
This value should be lower
than [1-08] as for high outdoor
temperatures
colder
water
is
required.
Leaving water temperature: Additional zone
Only applicable if 2 leaving water temperature zones are present.