Installation manual

 

1

 

ERYQ005~007ABV3

 

Outdoor unit for air to water heat pump

 

3P177782-1B

 

C

 

ONTENTS

 

Page

 

Safety precautions............................................................................. 1

Accessories....................................................................................... 2

Installation guidelines........................................................................ 2

 

Precautions for selecting the location ........................................................ 2
Selecting a location in cold climates .......................................................... 2
Refrigerant piping specifications................................................................ 3
Installing near a wall or obstacle................................................................ 3
Outdoor unit installation drawing ............................................................... 3

 

Installation procedure........................................................................ 4

 

Mounting the outdoor unit .......................................................................... 4
Drain work.................................................................................................. 4
Flaring the pipe end ................................................................................... 4
Connecting the refrigerant piping to the outdoor unit ................................ 4
Refrigerant piping work.............................................................................. 5
Purging air and checking gas leakage....................................................... 5
Charging refrigerant................................................................................... 6
Wiring ........................................................................................................ 6

 

Test run and final check .................................................................... 8

 

Trial operation and testing.......................................................................... 8
Items to check............................................................................................ 8

 

Pump down operation ....................................................................... 8

 

Pump down procedure............................................................................... 8
Forced cooling operation ........................................................................... 8

 

Disposal requirements ...................................................................... 8

 

S

 

AFETY

 

 

 

PRECAUTIONS

 

 

This manual classifies the precautions into WARNING and
CAUTION. Be sure to follow all the precautions below: they are
all important for ensuring safety.

 

 

The following safety symbols are used throughout this manual.

 

 

After completing installation, test the unit to check for installation
errors. Give the user adequate instructions concerning the use
and cleaning of the unit as included in the operation manual of
the indoor unit.

 

Warnings

 

 

Installation should be left to the dealer or another professional.
Improper installation may cause water leakage, electrical shock,
or fire.

 

 

Install the outdoor unit according to the instructions given in this
manual.
Incomplete installation may cause water leakage, electrical
shock, or fire.

 

 

Be sure to use the supplied or specified installation parts.
Use of other parts may cause the unit to vibrate loose, and may
cause water leakage, electrical shock, or fire.

 

 

Install the outdoor unit on a solid base that can support the
weight of the unit.
An inadequate base or incomplete installation may cause injury
in the event the unit falls off the base.

 

 

Electrical work must be carried out in accordance with the
installation manual and the national electrical wiring rules or
code of practice.
Insufficient capacity or incomplete electrical work may cause
electrical shock or fire.

 

 

Be sure to use a dedicated power circuit. Never use a power
circuit shared by another appliance.

 

 

For wiring, use a cable long enough to cover the entire distance
with no connection. Do not use an extension cord. Do not put
other loads on the power supply, use a dedicated power circuit.
Failure to do so may cause abnormal heat, electric shock, or fire.

 

 

Use the specified types of wires for electrical connections
between the indoor and outdoor unit.
Firmly clamp the interconnecting wires so that their terminals
receive no external stress. Incomplete connections or clamping
may cause terminal overheating or fire.

 

 

After connecting the interconnecting and supply wiring, be sure
to shape the cables so that they do not put undue force on the
electrical covers or panels.
Install covers over the wires. Incomplete cover installation may
cause terminal overheating, electrical shock, or fire.

 

 

If any refrigerant has leaked out during the installation
work, ventilate the room.
The refrigerant produces a toxic gas if exposed to
flames.

 

 

After all installation is complete, check to make sure
that no refrigerant is leaking.
The refrigerant produces a toxic gas if exposed to
flames.

 

 

When installing or relocating the system, be sure to keep the
refrigerant circuit free from substances other than the specified
refrigerant (R410A), such as air.
Any presence of air or other foreign substance in the refrigerant
circuit causes an abnormal pressure rise or rupture, resulting in
injury.

 

 

During pump down operation, stop the compressor before
removing the refrigerant piping.
If the compressor is still running and the stop valve is open
during pump-down, air will be sucked in when the refrigerant
piping is removed, causing abnormal pressure in the freezer
cycle which will lead to breakage and even to injury.

 

ERYQ005ABV3
ERYQ006ABV3
ERYQ007ABV3

 

Outdoor unit for air to water heat pump

 

Installation manual

 

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

 

Failure to follow any of WARNING is likely to result in such
grave consequences as death or serious injury.

Failure to follow any of CAUTION may in some cases result
in grave consequences.

Be sure to observe this instruction.

Be sure to establish an earth connection.

Never attempt.

Summary of Contents for Altherma ERYQ005ABV3

Page 1: ...INSTALLATION MANUAL ERYQ005ABV3 ERYQ006ABV3 ERYQ007ABV3 Outdoor unit for air to water heat pump ...

Page 2: ...e an extension cord Do not put other loads on the power supply use a dedicated power circuit Failure to do so may cause abnormal heat electric shock or fire Use the specified types of wires for electrical connections between the indoor and outdoor unit Firmly clamp the interconnecting wires so that their terminals receive no external stress Incomplete connections or clamping may cause terminal ove...

Page 3: ...o that the operation noise will cause no trouble There must be sufficient space for carrying the unit into and out of the site There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet The site must be free from the possibility of flammable gas leakage in a nearby place Locate the unit so that the noise and the discharged hot air will not annoy the ...

Page 4: ...een outdoor unit and indoor unit 3 m Maximum allowable height difference between outdoor unit and indoor unit 15 m Additional refrigerant required for refrigerant pipe exceeding 10 m in length 20 g m Gas pipe outer diameter 15 9 mm 5 8 Liquid pipe outer diameter 6 4 mm 1 4 100 350 1200 50 50 350 100 100 350 50 1 Wrap the insulation pipe with finishing tape from bottom to top 2 Service cover 3 Stop...

Page 5: ...the flare nut from the stop valve and put the flare nut on the pipe 4 Flare the pipe Set exactly at the position shown below 5 Check that the flaring is properly made Connecting the refrigerant piping to the outdoor unit 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare use refrigeration oil for R410A 2 Align the centres of both flares and tight...

Page 6: ...ssure valve Lo and completely close its high pressure valve Hi The high pressure valve subsequently requires no operation 3 Apply vacuum pumping Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the coupling meter needle does not go back 5 Remove the covers from t...

Page 7: ...imilar Be sure to use tools exclusively for R410A to ensure required pressure resistance and to prevent foreign materials from mixing into the system Wiring Procedure 1 Strip the insulation from the wire 20 mm 2 Connect the connection wires between the indoor and outdoor units so that the terminal numbers match see wiring diagram below Tighten the terminal screws securely We recommend a flathead s...

Page 8: ...urely 3 NOTE This unit must be earthed For earthing follow the applicable local standard for electrical installations 1 Single core wire 2 Screw 3 Flat washer 1 Round crimp style terminal 2 Screw 3 Flat washer A A AA 2 3 1 1 3 2 3 3 2 1 1 B B L N 1 2 3 1 3 2 CAUTION 1 In case the use of stranded conductor wires is unavoidable for one reason or another make sure to install round crimp style termina...

Page 9: ...ocal and national legislation NOTE Remark that during the first running period of the unit required power input may be higher than stated on the nameplate of the unit This phenomenon originates from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If the syst...