14
|
Troubleshooting
Installer reference guide
257
ERGA04~08E + 23E
Daikin Altherma 3 R F
4P629090-1C – 2022.08
14.3.8 Symptom: The space is NOT sufficiently heated at low outdoor temperatures
Possible causes
Corrective action
The backup heater operation is not
activated
Check the following:
▪
The backup heater operation mode is
enabled.
Go
to:
[9.3.8]:
Installer
settings
>
Backup heater
>
Operation
[4‑00]
▪
The backup heater overcurrent circuit
breaker is on. If not, turn it back on.
▪
The thermal protector of the backup
heater is NOT activated. If it has,
check the following, and then press
the reset button in the switch box:
-
The water pressure
-
Whether there is air in the system
-
The air purge operation
The backup heater equilibrium
temperature has not been configured
correctly
Increase the equilibrium temperature to
activate the backup heater operation at
a higher outdoor temperature.
Go to: [9.3.7]:
Installer settings
>
Backup heater
>
Equilibrium
temperature
[5‑01]
There is air in the system.
Purge air manually or automatically. See
the air purge function in the chapter
232].
Too much heat pump capacity is used
for heating domestic hot water
Check if the
Space heating
priority
settings have been
configured appropriately:
▪
Make sure that the
Space heating
priority
has been enabled.
Go
to
[9.6.1]:
Installer
settings
>
Balancing
>
Space
heating priority
[5‑02]
▪
Increase the "space heating priority
temperature" to activate backup
heater operation at a higher outdoor
temperature.
Go
to
[9.6.3]:
Installer
settings
>
Balancing
>
Priority temperature
[5‑03]
Summary of Contents for Altherma ERGA04E V3 Series
Page 293: ...11 11...
Page 294: ......
Page 295: ......
Page 296: ...4P629090 1C 2022 08 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...