5 Application guidelines
Installer reference guide
11
EPGA11~ EAVH/9W
Daikin Altherma – Low temperature split
4P556070-1 – 2018.10
5.2.1
Single room
Under floor heating or radiators – Wired room
thermostat
Setup
B
A
a
A
Main leaving water temperature zone
B
One single room
a
User interface used as room thermostat
▪ The under floor heating or radiators are directly connected to the
indoor unit.
▪ The room temperature of the main room is controlled by the user
interface used as a room thermostat (optional equipment BRC1H).
Configuration
Setting
Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
2 (Room thermostat): Unit
operation is decided based on
the ambient temperature of the
user interface.
Number of water temperature
zones:
▪ #: [4.4]
▪ Code: [7-02]
0 (Single zone): Main
Benefits
▪
Highest comfort and efficiency
. The smart room thermostat
functionality can decrease or increase the desired leaving water
temperature based on the actual room temperature (modulation).
This results in:
▪ Stable room temperature matching the desired temperature
(higher comfort)
▪ Less ON/OFF cycles (more quiet, higher comfort and higher
efficiency)
▪ Lowest possible leaving water temperature (higher efficiency)
▪
Easy
. You can easily set the desired room temperature via the
user interface:
▪ For your daily needs, you can use preset values and schedules.
▪ To deviate from your daily needs, you can temporarily overrule
the preset values and schedules, use the holiday mode.
Under floor heating or radiators – Wireless room
thermostat
Setup
B
A
b
a
A
Main leaving water temperature zone
B
One single room
a
Receiver for wireless external room thermostat
b
Wireless external room thermostat
▪ The under floor heating or radiators are directly connected to the
indoor unit.
▪ The room temperature is controlled by the wireless external room
thermostat (optional equipment EKRTR1).
Configuration
Setting
Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Number of water temperature
zones:
▪ #: [4.4]
▪ Code: [7-02]
0 (Single zone): Main
External room thermostat for the
main
zone:
▪ #: [2.A]
▪ Code: [C-05]
1 (1 contact): When the used
external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition. No separation between
heating or cooling demand.
Benefits
▪
Wireless.
The Daikin external room thermostat is available in a
wireless version.
▪
Efficiency.
Although the external room thermostat only sends ON/
OFF signals, it is specifically designed for the heat pump system.
Heat pump convectors
Setup
B
A
a
A
Main leaving water temperature zone
B
One single room
a
Remote controller of the heat pump convectors
▪ The heat pump convectors are directly connected to the indoor
unit.
Summary of Contents for Altherma EPGA14DAV3
Page 103: ......