Installation of EKRP1AHTA is required.
2
Fix the cable with cable ties to the cable tie mountings.
7.6.17
To connect the safety thermostat (normal
closed contact)
1
Connect the safety thermostat (normal closed) cable to the
appropriate terminals as shown in the illustration below.
X5M
910
2
Fix the cable with cable ties to the cable tie mountings.
NOTICE
Make sure to select and install the safety thermostat
according to the applicable legislation.
In any case, to prevent unnecessary tripping of the safety
thermostat, it is recommended that …
▪ … the safety thermostat is automatically resettable.
▪ … the safety thermostat has a maximum temperature
variation rate of 2°C/min.
▪ … there is a minimum distance of 2 m between the
safety thermostat and the motorised 3‑way valve
delivered with the domestic hot water tank.
INFORMATION
After it is installed, do NOT forget to configure the safety
thermostat. Without configuration, the indoor unit will
ignore the safety thermostat contact.
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/9+10) as the safety
thermostat. It is only possible for the system to have
EITHER preferential kWh rate power supply OR a safety
thermostat.
7.7
Finishing the outdoor unit
installation
7.7.1
To finish the outdoor unit installation
1
Insulate and fix the refrigerant piping and interconnection cable
as follows:
f
b
a
e
d
c
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Liquid pipe
e
Liquid pipe insulation
f
Finishing tape
2
Install the service cover.
To close the outdoor unit
1
Close the switch box cover.
2
Mount the front plate and the side plate.
NOTICE
When closing the outdoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
7.8
Finishing the indoor unit
installation
7.8.1
To close the indoor unit
1
Reinstall the user interface panel.
2
Reinstall the switch box cover and close the switch box.
3
Reinstall the front panel.
NOTICE
When closing the indoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
8
Configuration
8.1
Overview: Configuration
This chapter describes what you have to do and know to configure
the system after it is installed.
Why
If you do NOT configure the system correctly, it might NOT work as
expected. The configuration influences the following:
▪ The calculations of the software
▪ What you can see on and do with the user interface
How
You can configure the system via the user interface.
▪
First time – Configuration wizard.
When you turn ON the user
interface for the first time (via the indoor unit), the configuration
wizard starts to help you configure the system.
▪
Restart the configuration wizard.
If the system is already
configured, you can restart the configuration wizard. To restart the
configuration wizard, go to Installer settings > Configuration
wizard. To access Installer settings, see
most used commands" on page 41
.
▪
Afterwards.
If necessary, you can make changes to the
configuration in the menu structure or the overview settings.