1.4
Freeze-up Protection Control
Outline
During cooling operation, the signals being sent from the hydro-box allow the operating frequency
limitation and then prevent freezing of the indoor heat exchanger. (The signal from the hydro-box must
be divided into the zones as the followings.
Conditions for start
controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from operation start.
Control in each
zone
A
Heat exchanger
thermistor temperature
Return / Reset zone
Up zone
Keep zone
Drooping zone
Stop zone
B
C
D
E