Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
└─ Backup heater
9.1
[5-0D]
R/W (*2)
R/O (*1)
(*3)
0: 230V, 1~ (*1) (*2)
1: 230V, 3~ (*2)
2: 400V, 3~ (*3)
9.1
[4-0A]
R/W
0: 1 (*1)
1: 1/1+2 (*2) (*3)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.1
[6-03]
R/W
0~10kW, step: 0,2kW
2
kW (*2)
3kW (*1)(*3)
9.1
[6-04]
R/O (*1)
R/W (*2)
(*3)
0~10kW, step: 0,2kW
0kW (*1)
4kW (*2)
6kW (*3)
└─ Main zone
9.1
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
9.1
R/W
0: Fixed
2: Weather dependent
9.1
R/W
0: No
1: Yes
9.1
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
9.1
[1-01]
R/W
10~25°C, step: 1°C
15°C
9.1
[1-02]
R/W
[9-01]~[9-00], step: 1°C
35°C
9.1
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
9.1
[1-06]
20
9.1
[1-07]
35
9.1
[1-08]
22
9.1
[1-09]
18
└─ Additional zone
9.1
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1
R/W
0: Fixed
2: Weather dependent
9.1
R/W
0: No
1: Yes
9.1
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.1
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
50°C
9.1
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.1
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
9.1
[0-04]
8
9.1
[0-05]
12
9.1
[0-06]
35
9.1
[0-07]
20
└─ Tank
9.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
9.1
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
9.1
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.1
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
└─ Domestic hot water
9.2.1
[E-05]
[E-06]
[E-07]
R/O
3: Integrated
9.2.2
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
9.2.4
[D-07]
R/W
0: No
1: Yes
└─ Back up heater
9.3.1
[E-03]
R/O
2: 3V (*1)
3: 6V (*2)
4: 9W (*3)
9.3.2
[5-0D]
R/W (*2)
R/O (*1)
(*3)
0: 230V, 1~ (*1) (*2)
1: 230V, 3~ (*2)
2: 400V, 3~ (*3)
9.3.3
[4-0A]
R/W
0: 1 (*1)
1: 1/1+2 (*2) (*3)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.3.4
[6-03]
R/W
0~10kW, step: 0,2kW
2
kW (*2)
3kW (*1)(*3)
9.3.5
[6-04]
R/O (*1)
R/W (*2)
(*3)
0~10kW, step: 0,2kW
0kW (*1)
4kW (*2)
6kW (*3)
9.3.6
[5-00]
R/W
0: Allowed
1: Not allowed
--
--
--
--
--
--
--
--
Additional capacity step 2
Equilibrium
Eco setpoint
Reheat setpoint
Domestic hot water
DHW pump
Solar
BUH type
Voltage
Configuration
Capacity step 1
Heat up mode
Comfort setpoint
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Schedule
Emitter type
Setpoint mode
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Control
Setpoint mode
Schedule
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Voltage
Configuration
Capacity step 1
Additional capacity step 2
Emitter type
4P495259-1A - 2017.11
(#) Setting is not applicable for this unit.
(*1) *3V_
(*2) *6V_
(*3) *9W