8/9
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
9.I
[8-04]
R/W
0~95 min, step: 5 min
95 min
9.I
[8-05]
R/W
0: No
1: Yes
9.I
[8-06]
R/W
0~10°C, step: 1°C
5°C
9.I
[8-07]
18
9.I
[8-08]
20
9.I
[8-09]
R/W
[9-01]~[9-00], step: 1°C
35°C
9.I
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
33°C
9.I
[8-0B]
13
9.I
[8-0C]
10
9.I
[8-0D]
16
9.I
[9-00]
R/W
[2-0C]=2:
37~65, step: 1°C
55°C
[2-0C]≠2:
37~55, step: 1°C
55°C
9.I
[9-01]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-02]
22
9.I
[9-03]
5
9.I
[9-04]
R/W
1~4°C, step: 1°C
1°C
9.I
[9-05]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-06]
R/W
[2-0D]=2:
37~65, step: 1°C
55°C
[2-0D]≠2:
37~55, step: 1°C
55°C
9.I
[9-07]
5
9.I
[9-08]
22
9.I
[9-0C]
R/W
1~6°C, step: 0,5°C
1 °C
9.I
[9-0D]
R/W
0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
9.I
[9-0E]
6
9.I
[C-00]
R/W
0: Solar priority
1: Heat pump priority
9.I
[C-01]
0
9.I
[C-02]
R/W
0: No
1: Bivalent
9.I
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.I
[C-04]
R/W
2~10°C, step 1°C
3°C
9.I
[C-05]
R/W
0: -
1: 1 contact
2: 2 contacts
9.I
[C-06]
R/W
0: -
1: 1 contact
2: 2 contacts
9.I
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
9.I
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
9.I
[C-09]
R/W
0: Normally open
1: Normally closed
9.I
[C-0A]
0
9.I
[D-00]
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
9.I
[D-01]
R/W
0: No
1: Active open
2: Active closed
3: Safety thermostat
9.I
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
9.I
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
9.I
[D-04]
R/W
0: No
1: Pwr consmp ctrl
9.I
[D-05]
R/W
0: Forced off
1: As normal
9.I
[D-07]
R/W
0: No
1: Yes
9.I
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
9.I
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
Additional running time for the maximum running time.
Allow modulation of the LWT to control the room temp?
Leaving water temperature maximum modulation.
--
--
What is the desired comfort main LWT in heating?
What is the desired eco main LWT in heating?
--
--
--
What is the maximum desired LWT for main zone in heating?
What is the mimimum desired LWT for main zone in heating?
--
--
Leaving water temperature overshoot temperature.
What is the mimimum desired LWT for add. zone in heating?
What is the maximum desired LWT for add. zone in heating?
--
--
Room temperature hysteresis.
Pump speed limitation
--
Domestic heating water priority.
--
Is an external backup heat source connected?
Bivalent activation temperature.
Bivalent hysteresis temperature.
What is the thermo request contact type for the main zone?
Which heaters are permitted if prefer. kWh rate PS is cut?
Contact type of preferential kWh rate PS installation?
Which type of DHW pump is installed?
Leaving water temperature compensation around 0°C.
What is the thermo request contact type for the add. zone?
What is the unit control method in space operation?
Which type of external sensor is installed?
What is the required alarm output contact type?
--
Is a demand PCB connected?
Is the pump allowed to run if prefer. kWh rate PS is cut?
Is a solar kit connected?
Is an external kWh meter used for power measurement?
Is an external kWh meter used for power measurement?
4P499575-1A - 2017.11
(#) Setting is not applicable for this unit.