8 Configuration
Installer reference guide
63
ERLQ004~008CA + EHVH/X04+08S18+26CB
Daikin Altherma – Low temperature split
4P384973-1A – 2016.02
#
Code
Description
N/A
[8-03]
Booster heater delay timer.
Only for EKHW
Start-up delay time for the booster heater
when domestic hot water mode is active.
▪ When domestic hot water mode is
NOT active, the delay time is
20 minutes.
▪ The delay time starts from booster
heater ON temperature.
▪ By adapting the booster heater delay
time versus the maximum running
time, you can find an optimal balance
between the energy efficiency and the
heat up time.
▪ If the booster heater delay time is set
too high, it might take a long time
before the domestic hot water reaches
its set temperature.
▪ The setting [8-03] is only meaningful if
setting [4-03]=1. Setting [4-03]=0/2/3
limits the booster heater automatically
in relation to heat pump operation time
in domestic water heating mode.
▪ Make sure that [8-03] is always in
relation with the maximum running
time [8-01].
Range: 20~95 minutes (default: 50).
N/A
[8-04]
Additional running time for the maximum
running time depending on the outdoor
temperature [4-02] or [F-01].
Range: 0~95 minutes (default: 95).
[8-02]: Anti-recycling time
t
1
0
1
0
[8-01]
[8-02]
[8-00]
1
Heat pump domestic water heating mode (1=active, 0=not
active)
2
Hot water request for heat pump (1=request, 0=no request)
t
Time
[8-03]: Booster heater delay timer
t
1
0
1
0
1
0
[8-03]
3
4
1
0
1
Booster heater operation (1=active, 0=not active)
2
Heat pump domestic water heating mode (1=active, 0=not
active)
3
Hot water request for booster heater (1=request, 0=no
request)
4
Hot water request for heat pump (1=request, 0=no request)
t
Time
[8-04]: Additional running time at [4-02]/[F-01]
t
T
A
t
T
A
0
[8-01]
[5-03]
[4-02]
[8-02]
[8-01]+
[8-04]
0
[8-01]
[F-01]
35°C
[8-02]
[8-01]+
[8-04]
T
A
Ambient (outdoor) temperature
t
Time
Anti-recycle time
Maximum running time domestic hot water
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by
the installer according to the applicable legislation.
#
Code
Description
[A.4.4.2]
[2‑00]
Operation day:
▪ 0: Each day
▪ 1: Monday
▪ 2: Tuesday
▪ 3: Wednesday
▪ 4: Thursday
▪ 5: Friday
▪ 6: Saturday
▪ 7: Sunday
[A.4.4.1]
[2‑01]
Disinfection
▪ 0: No
▪ 1: Yes
[A.4.4.3]
[2‑02]
Start time: 00~23:00, step: 1:00.