
6 Electrical installation
Installation manual
24
EWSAH/X06UD
Daikin Altherma 3 WS
4P675760-1C – 2023.02
2×
1×
X5M
1×
9 10
Q4L
3
Fix the cable with cable ties to the cable tie mountings.
NOTICE
Make sure to select and install the safety thermostat
according to the applicable legislation.
In any case, to prevent unnecessary tripping of the safety
thermostat, we recommend the following:
▪ The safety thermostat is automatically resettable.
▪ The safety thermostat has a maximum temperature
variation rate of 2°C/min.
▪ There is a minimum distance of 2 m between the safety
thermostat and the 3‑way valve.
INFORMATION
ALWAYS configure the safety thermostat after it is
installed. Without configuration, the unit will ignore the
safety thermostat contact.
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/9+10) as the safety
thermostat. Thus, the system can have EITHER
preferential kWh rate power supply OR a safety
thermostat.
6.14
To connect the brine low pressure
switch
Depending on the applicable legislation, you might have to install a
brine low pressure switch (field supply).
NOTICE
Mechanical.
We recommend to use a mechanical brine
low pressure switch. If an electrical brine low pressure
switch is used, capacitive currents might disturb the flow
switch operation causing an error on the unit.
NOTICE
Before disconnecting.
If you want to remove or
disconnect the brine low pressure switch, first set [C‑0B]=0
(brine low pressure switch not installed). If not, this causes
an error.
1
Open the following (see
"4.2.1 To open the indoor unit"
6]):
1
Top panel
1
3
2
2
User interface panel
3
Installer switch box cover
2
Connect the brine low pressure switch cable as shown in the
illustration below.
2×
1×
A16P/X13A/1+4
1×
S1PL
P<
b
a
c
a
Cut loop wires coming from A16P/X13A/1+4 (factory
mounted)
b
Splicing connectors (field supply)
c
Wires from the brine low pressure switch cable (field
supply)
3
Fix the cable with cable ties to the cable tie mountings.
6.15
To connect the thermostat for
passive cooling
INFORMATION
Restriction:
Passive cooling is only possible for:
▪ Heating only models
▪ Central water loop temperatures between 0 and 20°C
Wires: 2×0.75 mm²
—