17
|
Technical data
Installer reference guide
281
ERRA08~12E + EL23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05
17.3 Piping diagram: Indoor unit
A
Water side
s
Capillary tube
B
Refrigerant side
t
Pump (main/mixed zone)
C
Field installed (delivered with the unit)
u
Shut-off valve (recommended)
D
Field supplied
v
Non-return valve (recommended)
a1
Additional zone – Space heating/cooling – Water IN
(screw connection, 1")
w
Pressure reducing valve (recommended)
a2
Additional zone – Space heating/cooling – Water
OUT (screw connection, 1")
*x
Pressure relief valve (max. 10 bar (=1.0 MPa))
(mandatory)
b1
Main zone – Space heating/cooling – Water IN
(screw connection, 1")
*y
Tundish (mandatory)
b2
Main zone – Space heating/cooling – Water OUT
(screw connection, 1")
z
Expansion vessel (recommended)
c1
DHW – Cold water IN (screw connection, 3/4")
B2L
Flow sensor
c2
DHW – Hot water OUT (screw connection, 3/4")
B1PW
Space heating water pressure sensor
d
Recirculation connection
M1S
3-way valve (mixing valve for the main/mixed zone)
e1
Gas refrigerant IN (heating mode; condenser)
M3S
3-way valve (space heating/domestic hot water)
e2
Liquid refrigerant OUT (heating mode; condenser)
f1
Liquid refrigerant IN (cooling mode; evaporator)
Thermistors:
f2
Gas refrigerant OUT (cooling mode; evaporator)
R1T
Outlet water heat exchanger
g
Plate heat exchanger
R2T
Outlet water backup heater
h
Shut-off valve for service
R3T
Refrigerant liquid side
i
Flexible pipe
R4T
Inlet water
j
Expansion vessel
R5T, R8T
Tank
k
Magnetic filter/dirt separator
R7T
Main/mixed zone – water OUT
l
Safety valve
m
Automatic air purge
Connections: