Configuration
Installer reference guide
210
ERRA08~12E + EL23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05
Possible outcomes when quiet mode is set to Automatic
If...
Then quiet mode =...
Restrictions
enabled?
Restrictions
(time + level)
defined?
Schedule
programmed?
No
N/A
No
OFF
Yes
Follows schedule
Yes
No
No
OFF
Yes
Follows schedule
Yes
No
Follows restriction
Yes
▪
During restricted time:
If
restricted level is stricter than
scheduled level, then follows
restriction.
Else,
follows
schedule.
▪
Outside
restricted
time:
Follows schedule.
Electricity prices and gas price
Only applicable in combination with the bivalent function. See also
#
Code
Description
[7.5.1]
N/A
Electricity price
>
High
[7.5.2]
N/A
Electricity price
>
Medium
[7.5.3]
N/A
Electricity price
>
Low
[7.6]
N/A
Gas price
INFORMATION
Electricity price can only be set when bivalent is ON ([9.C.1] or [C-02]). These values
can only be set in menu structure [7.5.1], [7.5.2] and [7.5.3]. Do NOT use overview
settings.
To set the gas price
1
Go to [7.6]:
User settings
>
Gas price
.
2
Select the correct gas price.
3
Confirm the changes.
INFORMATION
Price value ranging from 0.00~990 valuta/kWh (with 2 significant values).
To set the electricity price
1
Go to [7.5.1]/[7.5.2]/[7.5.3]:
User settings
>
Electricity
price
>
High
/
Medium
/
Low
.
2
Select the correct electricity price.
3
Confirm the changes.