Daikin Altherma 3 H W Installation Manual Download Page 18

5 Configuration

Installation manual

18

EABH/9W

Daikin Altherma 3 H W

4P644479-1 – 2020.12

▪ In 

Weather  dependent

  LWT  setpoint  mode,  the  scheduled

actions consist of desired shift actions, either preset or custom.

#

Code

Description

[2.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

5.2.6

Configuration wizard: Additional zone

The  most  important  settings  for  the  additional  leaving  water  zone
can be set here.

Emitter type

For  more  info  about  this  functionality,  see 

"Configuration  wizard:

Main zone"

 [

4

 17].

#

Code

Description

[3.7]

[2‑0D]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

Control

The  control  type  is  displayed  here,  but  cannot  be  adjusted.  It  is
determined by the control type of the main zone. For more info about
the functionality, see 

"Configuration wizard: Main zone"

 [

4

 17].

#

Code

Description

[3.9]

N/A

▪ 0: 

Leaving  water

  if  the  control  type

of the main zone is 

Leaving water

.

▪ 1: 

External  room  thermostat

 if the

control  type  of  the  main  zone  is

External  room  thermostat

 or 

Room

thermostat

.

Setpoint mode

For  more  info  about  this  functionality,  see 

"Configuration  wizard:

Main zone"

 [

4

 17].

#

Code

Description

[3.4]

N/A

▪ 0: 

Fixed

▪ 1: 

WD heating, fixed cooling

▪ 2: 

Weather dependent

If  you  choose 

WD  heating,  fixed  cooling

  or 

Weather

dependent

, the next screen will be the detailed screen with weather-

dependent  curves.  Also  see 

"Detailed  screen  with  weather-

dependent curve"

 [

4

 18].

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Also see 

"Configuration wizard: Main zone"

 [

4

 17].

#

Code

Description

[3.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

5.2.7

Detailed screen with weather-dependent
curve

When  weather-dependent  (WD)  operation  is  active  the  desired
leaving  water  or  tank  temperature  is  determined  automatically
depending on the averaged outdoor temperature. When the outdoor
temperature is lower the leaving water or tank temperature will need
to be higher as the water pipes will be colder and vice versa.

Slope and offset

Define the weather-dependent curve by its slope and offset:

▪ Change  the 

slope

  to  differently  increase  or  decrease  the

temperature  of  the  leaving  water  for  different  ambient
temperatures.  For  example,  if  leaving  water  temperature  is  in

general  fine  but  at  low  ambient  temperatures  too  cold,  raise  the
slope  so  that  leaving  water  temperature  is  heated  increasingly
more at decreasingly lower ambient temperatures.

▪ Change  the 

offset

  to  equally  increase  or  decrease  the

temperature  of  the  leaving  water  for  different  ambient
temperatures. For example, if leaving water temperature is always
a bit too cold at different ambient temperatures, shift the offset up
to  equally  increase  the  leaving  water  temperature  for  all  ambient
temperatures.

Examples

Weather-dependent curve when slope is selected:

X1

X2

c

d

e

Y1

Y2

Y3

Y4

a

b

Weather-dependent curve when offset is selected:

Y1

Y2

Y3

Y4

X1

X2

a

b

c

d

e

Possible actions on this screen

Select slope or offset.

Increase or decrease the slope/offset.

When slope is selected: set slope and go to offset.

When offset is selected: set offset.

Confirm changes and return to the submenu.

2-points WD curve

The weather-dependent curve is defined by two setpoints:

▪ Setpoint (X1, Y2)

▪ Setpoint (X2, Y1)

Weather-dependent curve:

Y1

Y2

X1

X2

a

Summary of Contents for Altherma 3 H W

Page 1: ...Installation manual Daikin Altherma 3 H W English Installation manual Daikin Altherma 3 H W EABH16DF6V EABH16DF9W EABX16DF6V EABX16DF9W...

Page 2: ...y odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 19...

Page 3: ...pendent curve 18 5 2 8 Configuration wizard Tank 19 5 3 Settings menu 19 5 3 1 Main zone 19 5 3 2 Additional zone 19 5 3 3 Information 20 5 4 Menu structure Overview installer settings 21 6 Commission...

Page 4: ...5 35 C Domestic hot water production 5 35 C INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHBCONV Mind the measurement guidelines Maximum hei...

Page 5: ...above the heat exchanger coil The booster heater must be located above the heat exchanger coil NOTICE Performance Performance data for third party tanks CANNOT be provided and performance CANNOT be g...

Page 6: ...Overview 1 2 3 1 4 4 1 Front panel 2 Switch box cover 3 Switch box 4 User interface panel Open 1 Remove the front panel 2 2 1 3 2 If you have to connect electrical wiring remove the switch box cover...

Page 7: ...he drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable legislation 1 Co...

Page 8: ...circuit against freezing Add glycol to the water Glycol lowers the freezing point of the water Install freeze protection valves Freeze protection valves drain the water from the system before it can...

Page 9: ...se freeze protection valves to drain the water from the system before it can freeze Install freeze protection valves field supply at all lowest points of the field piping Normally closed valves locate...

Page 10: ...y factory mounted cable Power supply for backup heater CAUTION Do NOT push or place redundant cable length in the unit 4 4 3 To connect the main power supply 1 Connect the main power supply In case of...

Page 11: ...er phase c This equipment complies with EN IEC 61000 3 11 European International Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply...

Page 12: ...ck the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Connect the electricity meters cable to the appropriate terminals as shown in the...

Page 13: ...tat normally closed cable to the appropriate terminals as shown in the illustration below X5M 9 10 2 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the...

Page 14: ...be displayed Accessing settings Legend for tables You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding ta...

Page 15: ...st be set on the user interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting...

Page 16: ...nd the zone with the highest water temperature is configured as the additional zone NOTICE If there are 2 zones and the emitter types are wrongly configured water of high temperature can be sent towar...

Page 17: ...T in heating 0 Underfloor heating Maximum 55 C Variable 1 Fancoil unit Maximum 55 C Variable 2 Radiator Maximum 65 C Fixed 8 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 T...

Page 18: ...n 3 1 N A 0 No 1 Yes 5 2 7 Detailed screen with weather dependent curve When weather dependent WD operation is active the desired leaving water or tank temperature is determined automatically dependin...

Page 19: ...t up until the storage comfort temperature has been reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature p...

Page 20: ...44479 1 2020 12 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 5 3 3 Information Dealer information The installer can fill in his contact numb...

Page 21: ...librium temperature Operation 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running t...

Page 22: ...tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification labe...

Page 23: ...evel 414 2 Go to A 2 Commissioning Actuator test run 3 Select a test from the list Example Pump 4 Select OK to confirm Result The actuator test run starts It stops automatically when ready 30 min To s...

Page 24: ...in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete doc...

Page 25: ...diagram Indoor unit 3D120613A R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Shut...

Page 26: ...t pump convector Safety thermostat Safety thermostat Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless...

Page 27: ...ater pump output DHW pump Domestic hot water pump Electrical meters Electricity meters For safety thermostat For safety thermostat Inrush Inrush current Max load Maximum load English Translation Norma...

Page 28: ...thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation 2 core 2 core communication 2x0 75...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...4P644479 1 2020 12 Copyright 2018 Daikin 4P644479 1 0000000W Verantwortung f r Energie und Umwelt...

Reviews: