background image

5 Piping installation

Installation manual

14

ETSH/X(B)16P30+50E

Daikin Altherma 3 H HT ECH

O

4P679468-1B – 2022.09

5.2.4

To protect the water circuit against
freezing

About freeze protection

Frost can damage the system. To prevent the hydraulic components
from  freezing,  the  software  is  equipped  with  special  frost  protection
functions such as water pipe freeze prevention and drain prevention
(see the installer reference guide) that include the activation of pump
in case of low temperatures.

However,  in  case  of  a  power  failure,  these  functions  cannot
guarantee protection.

Do one of the following to protect the water circuit against freezing:

▪ Add  glycol  to  the  water.  Glycol  lowers  the  freezing  point  of  the

water.

▪ Install freeze protection valves. Freeze protection valves drain the

water  from  the  system  before  it  can  freeze.  Insulate  the  freeze
protection valves in a similar way as the water piping, but do NOT
insulate the inlet and outlet (release) of these valves.

NOTICE

If  you  add  glycol  to  the  water,  do  NOT  install  freeze
protection  valves. 

Possible  consequence: 

Glycol  leaking

out of the freeze protection valves.

Freeze protection by glycol

About freeze protection by glycol

Adding glycol to the water lowers the freezing point of water.

WARNING

Due  to  the  presence  of  glycol,  corrosion  of  the  system  is
possible.  Uninhibited  glycol  will  turn  acidic  under  the
influence  of  oxygen.  This  process  is  accelerated  by  the
presence  of  copper  and  high  temperatures.  The  acidic
uninhibited  glycol  attacks  metal  surfaces  and  forms
galvanic  corrosion  cells  that  cause  severe  damage  to  the
system. Therefore it is important that:

▪ the water treatment is correctly executed by a qualified

water specialist,

▪ a  glycol  with  corrosion  inhibitors  is  selected  to

counteract acids formed by the oxidation of glycols,

▪ no  automotive  glycol  is  used  because  their  corrosion

inhibitors  have  a  limited  lifetime  and  contain  silicates
which can foul or plug the system,

▪ galvanized pipes are NOT used in glycol systems since

the  presence  may  lead  to  the  precipitation  of  certain
components in the glycol's corrosion inhibitor.

NOTICE

Glycol  absorbs  water  from  its  environment.  Therefore  do
NOT add glycol that has been exposed to air. Leaving the
cap  off  the  glycol  container  causes  the  concentration  of
water  to  increase.  The  glycol  concentration  is  then  lower
than  assumed.  As  a  result,  the  hydraulic  components
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air.

NOTICE

Use  ONLY  propylene  glycol  including  the  required
inhibitors, classified as category III as per EN1717.

Required concentration of glycol

The  required  concentration  of  glycol  depends  on  the  lowest
expected  outdoor  temperature,  and  on  whether  you  want  to  protect
the  system  from  bursting  or  from  freezing.  To  prevent  the  system
from freezing, more glycol is required.

Add glycol according to the table below.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

–30°C

35%

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

NOTICE

▪ The  required  concentration  might  differ  depending  on

the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the  glycol  manufacturer.  If  necessary,  meet  the
requirements set by the glycol manufacturer.

▪ The  added  concentration  of  glycol  should  NEVER

exceed 35%.

▪ If the liquid in the system is frozen, the pump will NOT

be  able  to  start.  Mind  that  if  you  only  prevent  the
system from bursting, the liquid inside might still freeze.

▪ When  water  is  at  standstill  inside  the  system,  the

system is very likely to freeze and get damaged.

Glycol setting

NOTICE

If  glycol  is  present  in  the  system,  setting  [E-0D]  must  be
set to 1. If the glycol setting is NOT set correctly, the liquid
inside the piping can freeze.

Freeze protection by freeze protection valves

About freeze protection valves

When no glycol is added to the water, you can use freeze protection
valves to drain the water from the system before it can freeze.

▪ Install freeze protection valves (field supply) at all lowest points of

the field piping.

▪ Normally closed valves (located indoors near the piping entry/exit

points)  can  prevent  that  all  water  from  indoor  piping  is  drained
when the freeze protection valves open.

NOTICE

When  freeze  protection  valves  are  installed,  set  the
minimum cooling setpoint (default=7°C) at least 2°C higher
than  the  maximum  opening  temperature  of  the  freeze
protection  valve.  If  lower,  freeze  protection  valves  can
open during cooling operation.

For more information, see the installer reference guide.

5.2.5

To fill the heat exchanger inside the
storage tank

Following  heat  exchanger  have  to  be  filled  with  water  before  the
storage tank can be filled:

▪ The domestic hot water heat exchanger

Summary of Contents for Altherma 3 H HT ETSXB16E7

Page 1: ...kin Altherma 3 H HT ECH O English Installation manual Daikin Altherma 3 H HT ECH O ETSH16P30E ETSH16P50E ETSHB16P30E ETSHB16P50E ETSX16P30E ETSX16P50E ETSXB16P30E ETSXB16P50E A B C Z 1 2 3 9 https dai...

Page 2: ...edpisy za p edpokladu e tyto v robky jsou pou v ny v souladu s na imi pokyny u skladu sa sljede om direktivom ma ili odredbom a uz uvjet da se proizvodi koriste sukladno na im uputama megfelelnek az...

Page 3: ...o p edpisy za p edpokladu e tyto v robky jsou pou v ny v souladu s na imi pokyny u skladu sa sljede om direktivom ma ili odredbom a uz uvjet da se proizvodi koriste sukladno na im uputama megfelelnek...

Page 4: ...ivered as accessory 27 6 3 15 To connect the solar input 27 6 3 16 To connect the DHW output 28 7 Configuration 28 7 1 Overview Configuration 28 7 1 1 To access the most used commands 29 7 2 Configura...

Page 5: ...d regulations Installation site see 4 1 Preparing the installation site 47 WARNING Follow the service space dimensions in this manual for correct installation of the unit See 4 1 1 Installation site r...

Page 6: ...ting electrical shock or fire Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing capacitor will reduce performance and may cause accidents WARN...

Page 7: ...covers on the plugs 4 Unit installation 4 1 Preparing the installation site 4 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the...

Page 8: ...nd slide the interface panel downwards 1 2 2 Remove the switch box cover NOTICE Do NOT damage or remove the foam sealing of the switch box 3 Disconnect the ground connection from the top cover of the...

Page 9: ...stall the indoor unit 1 Lift the indoor unit from the pallet and place it on the floor Also see 3 1 2 To handle the indoor unit 47 2 Connect the drain hose to the drain See 4 3 2 To connect the drain...

Page 10: ...Pa Water pressure Storage tank The water inside the storage tank is not pressurized Therefore a visual check of the water level in the storage tank has to be carried out annually Water temperature All...

Page 11: ...the piping is aligned properly Deformation of the piping can cause malfunctioning of the unit 1 Connect the outdoor unit field piping to the water connection pipes of the indoor unit Do NOT exceed the...

Page 12: ...cooling water IN screw connection 1 c Domestic hot water OUT screw connection 1 d Domestic cold water IN cold water supply screw connection 1 NOTICE It is recommended to install shut off valves on th...

Page 13: ...ressure vessel in an easily accessible place maintenance parts replacement 5 2 3 To fill the heating system DANGER RISK OF ELECTROCUTION During the filling process water can escape from any leaking po...

Page 14: ...eze up after all Take preventive actions to ensure a minimal exposure of the glycol to air NOTICE Use ONLY propylene glycol including the required inhibitors classified as category III as per EN1717 R...

Page 15: ...aks 5 2 6 To fill the storage tank NOTICE Before the storage tank can be filled the heat exchangers inside the storage tank have to be filled see previous chapters Fill the storage tank with a water p...

Page 16: ...source control See 6 3 10 To connect the changeover to external heat source 423 Power consumption digital inputs See 6 3 11 To connect the power consumption digital inputs 424 Safety thermostat See 6...

Page 17: ...t Installation manual of the wired room thermostat digital or analogue multi zoning base unit Addendum book for optional equipment In this case You need to connect the wired room thermostat digital or...

Page 18: ...of normal kWh rate power supply Interconnection cable Wires 3 GND 1 5 mm Power supply indoor unit Wires 1N GND Maximum running current 6 3 A A 2x B X1M 1 2 3 4 5 6 A B 2x b a a 1 2 3 b L N F2B 1 3 2 4...

Page 19: ...ccordance with the backup heater capacity as listed in the table below Backup heater type Backup heater capacity Power supply Maximum running current Zmax 3V 1 kW 1N 230 V 4 4 A 2 kW 1N 230 V 8 7 A 3...

Page 20: ...3 4 F1B 32A I I 9W 3N 400 V 3N 50 Hz 400 V AC SWB2 Q1DI L1 L2 L3 N X6M 1 2 3 4 5 6 F1B 20A I I I F1B Overcurrent fuse field supply Recommended fuse tripping class C Q1DI Earth leakage circuit breaker...

Page 21: ...p cover 2 Connect the valve control cable to the appropriate terminals as shown in the illustration below NOTICE Wiring is different for a NC normally closed valve and a NO normally open valve A B M2S...

Page 22: ...door unit 48 1 User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top cover 2 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below B A...

Page 23: ...e space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below A B B 5 6 X 2M 1 N L Space C H On OFF output Max load 0 3 A 230 V AC 1 A 5 V DC 5 6 A 3 Fix...

Page 24: ...following see 4 2 1 To open the indoor unit 48 1 User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top cover 2 Install the switch box metal insert 1 2 3 3 Connect the power consumption d...

Page 25: ...ermostat after it is installed Without configuration the unit will ignore the safety thermostat contact 6 3 13 To connect a Smart Grid This topic describes 2 possible ways to connect the indoor unit t...

Page 26: ...id in case of high voltage contacts is as follows S4S 9 10 X 5M 1 X 5M 1 7 8 K2A K1A 5 6 3 4 K1A L N L N STEP 3 a b c d e f STEP 1 STEP 2 A1 A2 25 24 25 23 X1 M 2 K2A A1 A2 2 1 STEP 1 Smart Grid relay...

Page 27: ...he high voltage wiring as follows A B A B X 2M 1 24 25 X M 12 25 X M 12 24 X M 12 25 X M 12 23 1 2 23 L2 L1 N N 6 Fix the cable with cable ties to the cable tie mountings General information see 6 3 1...

Page 28: ...M 1 11 12 A B DHW output Max load 0 3 A 230 V AC 12 11 3 Fix the cable with cable ties to the cable tie mountings General information see 6 3 1 To connect the electrical wiring to the indoor unit 417...

Page 29: ...in code for the user permission level Browse through the list of digits and change the selected digit Move the cursor from left to right Confirm the pin code and proceed Installer pin code The Install...

Page 30: ...screen and confirm whether the backup heater can take over the heat load or not Alternatively when Emergency is set to auto SH reduced DHW on space heating is reduced but domestic hot water is still...

Page 31: ...ackup heater The capacities for the different steps of the backup heater must be set for the energy metering and or power consumption control feature to work properly When measuring the resistance val...

Page 32: ...imum 55 C Variable 2 Radiator Maximum 70 C Fixed 10 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means that for a same leaving water temperature setpoint the average e...

Page 33: ...ure varies according to the tank temperature schedule See the operation manual for more details Settings for Reheat only mode During Reheat only mode the tank setpoint can be set on the user interface...

Page 34: ...rature of the leaving water for different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so that leaving wate...

Page 35: ...triction Only available to installers 5 C Tank WD curve INFORMATION Maximum and minimum setpoints You cannot configure the curve with temperatures that are higher or lower than the set maximum and min...

Page 36: ...e in external room thermostat control For more info about the functionality see 7 4 1 Main zone 435 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 cont...

Page 37: ...eration mode Allow electrical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4...

Page 38: ...carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the in...

Page 39: ...water mode To monitor the temperatures 1 In the menu go to Sensors 2 Select the temperature information 8 2 4 To perform an actuator test run Purpose Perform an actuator test run to confirm the opera...

Page 40: ...all an electric backup heater to ensure safe operation for all conditions Drain back models For drain back models a backup heater EKECBUA must always be installed For drain back models the factory set...

Page 41: ...onnection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 1 b2 DHW Hot water OUT screw connection 1 c1 Water IN from outdoor unit screw connection 1 c2 Wa...

Page 42: ...FF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box Engl...

Page 43: ...ormally closed Normally open Normally open Note outputs can be taken from terminal positions X12M 17 L 18 N and X12M 17 L 11 N Max 2 outputs at once are possible this way Note outputs can be taken fro...

Page 44: ...M 3 4 2 core 2x0 75 2 core 2x0 75 X15M 7 8 X15M 8 X15M 7 2 Safety thermostat Q4L 2 1 Smartgrid contact K1A Smartgrid relais K1A Smartgrid relais K2A X12M 23 25 2 core 2x0 75 X12M 24 25 2 core 2x0 75 O...

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...4P679468 1B 2022 09 Copyright 2022 Daikin 4P679468 1 B 0000000B Verantwortung f r Energie und Umwelt...

Reviews: