7
|
Installation
Installer reference guide
89
EPGA11~ EAV23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
b
f
a
e
e
d
c
e
e
e
a
Power supply cable
b
Communication cable
c
Cable for bottom plate heater (optional)
d
Ferrite core
e
Tie strap
f
Compressor
NOTICE
To guarantee electromagnetic compatibility:
▪
Make sure both power supply and communication cables run parallel to one
another. Use tie straps to hold the cables together.
▪
Make sure the cables are located as far away from the compressor as possible.
▪
The communication cable MUST pass through the ferrite core.
5
Make sure that the cable does NOT come in contact with sharp edges or hot
gas piping.
6
Install the switch box cover.
INFORMATION
When installing field supply or option cables, foresee sufficient cable length. This will
make it possible to remove/reposition the switch box and gain access to other
components during service.
CAUTION
Do NOT push or place redundant cable length in the unit.
7.6.7 To connect the electrical wiring on the indoor unit
1
To open the indoor unit, see
"7.2.3 To open the indoor unit"
2
The wiring enters the unit from the top: