14
|
Technical data
Installer reference guide
215
EPGA11~ EAV23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
14.6 ESP curve: Indoor unit
Note:
A flow error will occur when the minimum water flow rate is not reached.
4D120998
B (l/min)
0
40
60
80
100
30
50
70
90
110
20
0
5
10
15
20
25
30
35
40
45
50
55
60
65
10
120
C
A (kPa)
A
External static pressure in the space heating/cooling circuit
B
Water flow rate through the unit in the space heating/cooling circuit
C
Operation range
Dashed lines:
Operation area is extended to lower flow rates only in case the unit
operates with heat pump only. (Not in startup, no backup heater operation, no
defrost operation.)
Notes:
▪
Selecting a flow outside the operating area can damage the unit or cause the unit
to malfunction. See also the minimum and maximum allowed water flow range in
the technical specifications.
▪
Water quality must be according to EU directive 98/83 EC.
14.7 Technical specifications: Domestic hot water tank
14.7.1 Test results in accordance with EN12897 (2016)
Description
Test result
Hot water capacity
160 l
Reheat time
14 min
INFORMATION
This unit has been tested and approved according to BS EN12897:2016