3 Unit installation
Installation manual
8
EGSAH/X06+10DA9W(G)
Daikin Altherma 3 GEO
4P569811-1C – 2020.07
3
Remove the clips that lock the valves in place.
4
Uncouple the piping.
4×
5
Remove the lower hydro module cover.
4×
T25
6
Unlink the connectors that run from the hydro module to the
main switch box or other locations. Route the wires through the
grommets of the upper hydro module cover.
X22Y
X11YB
X803YA
X1YA
7
Remove the upper hydro module cover. You can lift up the
uncoupled piping to access the screws more easily, and to take
off the cover itself.
5×
T25
8
Remove the screw that fixes the hydro module to the bottom
plate.
1×
T25
9
Lift the uncoupled piping and use the handle on the front of the
module to carefully slide the module out of the unit. Make sure
the module remains level and does not tilt forward.
CAUTION
The hydro module is heavy. It requires at least two persons
to carry it.
NOTICE
Make sure not to damage any insulation during the