Daikin Altherma EHS(X/H)(B)-D
Heat pump (indoor unit) with integrated heat accumulator
008.1444099_01 – 11/2018 – EN
Malfunction
Possible cause
Possible solution
Internal circulation
pump generates ex-
cessively high operat-
ing noises
Air in the water circuit.
▪ Completely vent the heating system and the internal circula-
tion pump.
Noises caused by vibrations.
▪ Check the indoor unit, its components and covers to ensure
they are fastened correctly.
Bearing damage in the internal circulation pump
▪ Replace the internal circulation pump.
Water pressure at pump inlet too low.
▪ On the controller [→ Main menu → Information → Overview],
check that sufficient water pressure (> 0.5 bar) is available.
▪ Check that the pressure gauge is working correctly (connec-
tion of an external pressure gauge).
▪ Check the admission pressure in the expansion tank and wa-
ter pressure; if necessary, top up the heating water and adjust
the admission pressure.
Safety pressure relief
valve is leaking or al-
ways open
Expansion tank is defective.
▪ Replace the expansion tank.
Water pressure in heating system is too high.
▪ On the controller [→ Main menu → Information → Overview],
check that the water pressure is below the specified maximum
pressure. If necessary, drain sufficient water until the pressure
is in the middle of the permissible range.
Safety pressure relief valve is stuck.
▪ Check the safety pressure relief valve and if necessary, re-
place it.
▪ Turn the red knob on the safety pressure relief valve anti-
clockwise. If you can hear a rattling noise, the safety pres-
sure relief valve needs replacing.
Tab. 8-1
Possible malfunctions
8.3
Fault codes
Code
Component/Designation
Error
Possible fault rectification
E75
Inflow temperature sensor
t
V, BH
Inflow temperature sensor error
Inflow temperature sensor defective.
▪ Check, replace.
E76
Storage tank temperature
sensor t
DHW1
Storage tank temperature sensor error
Storage tank temperature sensor t
DHW1
or connecting
cable defective or not connected.
▪ Check, replace.
▪ Check the [Tank temperature sensor] setting.
E81
RoCon BM2C printed circuit
board
Communication fault
Parameter storage in the EEPROM corrupted.
▪ Contact a service technician.
E88
RoCon BM2C printed circuit
board
Parameter storage in the external flash memory cor-
rupted.
▪ Contact a service technician.
E91
Connected CAN modules
CAN module bus ID duplicated, set unique data bus
address.
E128
Return flow temperature
sensor t
R1
Return flow temperature sensor error
Return flow temperature sensor t
R1
in FLS flow
sensor connecting cable defective.
▪ Check, replace.
E129
Pressure sensor DS
Pressure sensor error
Pressure sensor DS defective.
▪ Check, replace.