OMM 1166-1
AGZ 025D through 190D
29
Circuit Functions
Definitions
Refrigerant Saturated Temperature
Refrigerant saturated temperature shall be calculated from the pressure sensor readings for each circuit.
Evaporator Approach
The evaporator approach shall be calculated for each circuit. The equation is as follows:
Evaporator Approach = LWT – Evaporator Saturated Temperature
Condenser Approach
The condenser approach shall be calculated for each circuit. The equation is as follows:
Condenser Approach = Condenser Saturated Temperature - OAT
Suction Superheat
Suction superheat shall be calculated for each circuit using the following equation:
Suction superheat = Suction Temperature – Evaporator Saturated Temperature
Pumpdown Pressure
The pressure to which a circuit will pumpdown is based on the Low Evaporator Pressure Unload set point.
The equation is as follows:
Pumpdown pressure = Low Evap Pressure Unload set point – 103KPA (15 PSI)
Circuit Control Logic
Circuit Enabling
A circuit should be enabled to start if the following conditions are true:
Circuit switch is closed
No circuit alarms are active
Circuit Mode set point is set to Enable
At least one compressor is enabled to start (according to enable setpoints)
Compressor Availability
A compressor is considered available to start if all the following are true:
The corresponding circuit is enabled
The corresponding circuit is not in pumpdown
No cycle timers are active for the compressor
No limit events are active for the corresponding circuit
The compressor is enabled via the enable setpoints
The compressor is not already running
Circuit States
The circuit will always be in one of four states:
Off – Circuit is not running
Preopen – Circuit is preparing to start
Run – Circuit is running
Pumpdown – Circuit is doing a normal shutdown