Alarms Generated by the Basic Control Panel
Table 69: Alarms Generated by the Basic Control Panel
The Basic Control Panel indicates Control Panel alarms with a code, A5xxx .
ALARM
CODE
CAUSE
WHAT TO DO
5001
Drive is not responding .
Check panel connection .
5002
Incompatible communication profile
Contact your local Daikin representative .
5010
Corrupted panel parameter backup file
Retry parameter upload . Retry parameter download .
5011
Drive is controlled from another source .
Change drive control to local control mode .
5012
Direction of rotation is locked .
Enable change of direction . See parameter 1003 DIRECTION, page 38 .
5013
Panel control is disabled because start inhibit is active .
Start from the panel is not possible . Reset the emergency stop command
or remove the 3-wire stop command before starting from the panel . See
parameters 1001 EXT1 COMMANDS, 1002 EXT2 COMMANDS and 2109
EMERG STOP SEL .
5014
Panel control is disabled because of drive fault .
Reset drive fault and retry .
5015
Panel control is disabled because local control mode lock is active .
Deactivate local control mode lock and retry . See parameter 1606 LOCAL
5018
Parameter default value is not found .
Contact your local Daikin representative .
5019
Writing non-zero parameter value is prohibited .
Only parameter reset is allowed .
5020
Parameter or parameter group does not exist or parameter value is
inconsistent .
Contact your local Daikin representative .
5021
Parameter or parameter group is hidden .
Contact your local Daikin representative .
5022
Parameter is write protected .
Parameter value is read-only and cannot be changed .
5023
Parameter change is not allowed, when drive is running .
Stop drive and change parameter value .
5024
Drive is executing task .
Wait until task is completed .
5025
Software is being uploaded or downloaded .
Wait until upload/download is complete .
5026
Value is at or below minimum limit .
Contact your local Daikin representative .
5027
Value is at or above maximum limit .
Contact your local Daikin representative .
5028
Invalid value
Contact your local Daikin representative .
5029
Memory is not ready .
Retry .
5030
Invalid request
Contact your local Daikin representative .
5031
Drive is not ready for operation, eg due to low DC voltage .
Check input power supply .
5032
Parameter error
Contact your local Daikin representative .
5040
Parameter download error . Selected parameter set is not in current
parameter backup file.
Perform upload function before download .
5041
Parameter backup file does not fit into memory.
Contact your local Daikin representative .
5042
Parameter download error . Selected parameter set is not in current
parameter backup file.
Perform upload function before download .
5043
No start inhibit
—
5044
Parameter backup file restoring error
Check that file is compatible with drive.
5050
Parameter upload aborted
Retry parameter upload .
5051
File error
Contact your local Daikin representative .
5052
Parameter upload has failed .
Retry parameter upload .
5060
Parameter download aborted
Retry parameter download .
5062
Parameter download has failed .
Retry parameter download .
5070
Panel backup memory write error
Contact your local Daikin representative .
5071
Panel backup memory read error
Contact your local Daikin representative .
5080
Operation is not allowed because drive is not in local control mode .
Switch to local control mode .
5081
Operation is not allowed because of active fault .
Check cause of fault and reset fault .
5083
Operation is not allowed because parameter lock is on .
Check parameter 1602 PARAMETER LOCK setting .
5084
Operation is not allowed because drive is performing task .
Wait until task is completed and retry .
5085
Parameter download from source to destination drive has failed .
Check that source and destination drive types are same, i .e . ACS320 . See the
type designation label of the drive .
5086
Parameter download from source to destination drive has failed .
Check that source and destination drive type designations are the same . See
type designation labels of the drives .
5087
Parameter download from source to destination drive has failed because
parameter sets are incompatible .
Check that source and destination drive information are same . See parameters
in Group 33: Information, page 56 .
5088
Operation has failed because of drive memory error .
Contact your local Daikin representative .
5089
Download has failed because of CRC error .
Contact your local Daikin representative .
5090
Download has failed because of data processing error .
Contact your local Daikin representative .
5091
Operation has failed because of parameter error .
Contact your local Daikin representative .
5092
Parameter download from source to destination drive has failed because
parameter sets are incompatible .
Check that source and destination drive information are same . See parameters
in Group 33: Information, page 56 .
f
aulT
T
raCIng
www .DaikinApplied .com 93
OM 1190-1 • MD4 VFD