Analog Input Object Instance Summary
The following table summarizes the Analog Input Objects supported:
Table 64: Analog Input Object Instance Summary
Instance ID
Object Name Description
Units
Present Value
Access Type
AI0
ANALOG
INPUT 1
This object indicates the value of Analog Input 1 . The corresponding drive parameter is 0120 .
Percent
R
AI1
ANALOG
INPUT 2
This object indicates the value of Analog Input 2 . The corresponding drive parameter is 0121 .
Percent
R
AO0
AO 1
COMMAND
This object controls Analog Output 1 . The corresponding drive parameter is 0135, COMM
VALUE 1 . Control requires parameter 1501 value = 135 .
Percent
C
NOTE:
For Present Value Access Types, R = Read-only,W = Writeable, C = Commandable .
Commandable values support priority arrays & relinquish defaults .
f