The chapter contains the technical specifications of the drive, eg ratings, sizes and technical requirements as well as
provisions for fulfilling the requirements for CE and other marks.
Table 73: Ratings, Types and Voltages
HP
Ratings
Frame Size
Input
Output
Nominal without
Reactor A
Nominal with 5%
Reactor A
Continous @ 50C,
10% Overload
1
A
Continous @ 40C,
0% Overload A
Instantaneous
Peak
2
A
1-phase supply voltage 200 - 240 V units (Confirm output ratings meet motor requirements)
0 .5
11 .4
N/A
4 .5
4 .7
7 .9
R1
1 .0
16 .1
N/A
6 .5
6 .7
11 .4
R1
2 .0
16 .8
N/A
7 .2
7 .5
12 .6
R2
3 .0
21 .0
N/A
9 .4
9 .8
16 .5
R2
3-phase supply voltage 200 - 240 V units
0 .5
8 .4
5 .2
4 .7
5 .2
8 .2
R1
2 .0
13 .2
8 .3
7 .5
8 .3
13 .1
R1
3 .0
15 .7
10 .8
9 .8
10 .8
17 .2
R2
5 .0
27 .3
19 .4
17 .6
19 .4
30 .8
R2
7 .5
45 .0
26 .8
24 .4
26 .8
42 .7
R3
10 .0
55 .0
34 .1
31 .0
34 .1
54 .3
R4
15 .0
76 .0
50 .8
46 .2
50 .8
80 .9
R4
3-phase supply voltage 380 - 480 V units
0 .5
2 .2
1 .2
1 .1
1 .2
2 .1
R0
1 .0
4 .1
2 .4
2 .2
2 .4
4 .2
R1
2 .0
6 .9
4 .1
3 .7
4 .1
7 .2
R1
3 .0
9 .6
5 .6
5 .1
5 .6
9 .8
R1
4 .0
11 .6
7 .3
6 .6
7 .3
12 .8
R1
5 .0
13 .6
8 .8
8 .0
8 .8
15 .4
R1
7 .5
18 .8
12 .5
11 .4
12 .5
21 .9
R3
10 .0
22 .1
15 .6
14 .2
15 .6
27 .3
R3
15 .0
30 .9
23 .1
21 .0
23 .1
40 .4
R3
20 .0
52 .0
31 .0
28 .2
31 .0
54 .3
R4
25 .0
61 .0
38 .0
34 .5
38 .0
66 .5
R4
30 .0
67 .0
44 .0
40 .0
44 .0
77 .0
R4
1) Overloadability for one minute every ten minutes .
2) Instantaneous peak current for two seconds every ten minutes .
OM 1190-1 • MD4 VFD 102 www .DaikinApplied .com
T
eCHnICal
d
aTa
Summary of Contents for ACS320
Page 115: ......