![Daikin ACQ71C/AZQS71BV1 Technical Data Manual Download Page 6](http://html1.mh-extra.com/html/daikin/acq71c-azqs71bv1/acq71c-azqs71bv1_technical-data-manual_3733613006.webp)
• Outdoor Unit • AZQS-BV1
2
• Split - Sky Air • AZQS-BV1
4
2
Specifications
Notes
(1) EER/COP according to Eurovent 2012, for use outside EU only
Seasonal efficiency
(according to
EN14825)
Cooling
Energy label
B
-
Pdesign
kW
6.80
9.50
-
SEER
4.65
4.60
-
Annual energy
consumption
kWh
512
723
-
Heating (Average
climate)
Energy label
A
-
Pdesign
kW
6.33
7.60
-
SCOP
3.80
-
Annual energy
consumption
kWh
2,332
2,800
-
Nominal efficiency
(cooling at 35°/27°
nominal load, heating
at 7°/20° nominal
load)
EER
3.03
2.62
2.63
3.01
COP
3.05
3.41
3.61
3.41
Annual energy consumption
kWh
1,120
1,810
2,300
2,159
Energy label
Cooling
B
D
-
Heating
D
B
A
-
2-4 Technical Specifications
AZQS71BV1
AZQS100BV1
AZQS125BV1
AZQS140BV1
Capacity control
Method
Inverter controlled
Casing
Colour
-
Ivory white
Material
-
Painted galvanized steel plate
Dimensions
Unit
Height
mm
770
990
1,430
Width
mm
900
940
Depth
mm
320
Packed unit
Height
mm
900
1,170
1,610
Width
mm
980
1,015
Depth
mm
420
422
Weight
Unit
kg
67
81
102
Packed unit
kg
71
88
108
Heat exchanger
Length
mm
857
-
Rows
Quantity
2
-
Fin pitch
mm
1.4
-
Passes
Quantity
8
-
Face area
m²
0.641
-
Stages
Quantity
34
-
Empty tubeplate
hole
Quantity
0
-
Tube type
Hi-XSS
-
Fin
Type
WF fin
Treatment
Anti-corrosion treatment (PE)
Compressor
Quantity
1
Model
2YC63DXD
-
Type
Hermetically sealed swing compressor
Output
W
1,700.0
-
Starting method
Inverter driven
-
Fan
Type
Propeller fan
Discharge direction
Horizontal
Quantity
1
2
Air flow rate
Cooling Nom.
m³/min
52.0
76
77
83
Super
low
m³/min
-
cfm
-
Heating Nom.
m³/min
48.0
83
62
Super
low
m³/min
-
cfm
-
2-3 Capacity and Power input
AHQ71C/AZQS71BV1
AHQ100C/AZQS100BV1
AHQ125C/AZQS125BV1
AHQ140C/AZQS140BV1
Summary of Contents for ACQ71C/AZQS71BV1
Page 1: ...Air Conditioning Technical Data EEDEN14 131A AZQS BV1...
Page 2: ......
Page 10: ...Outdoor Unit AZQS BV1 4 Split Sky Air AZQS BV1 8 4 Options 4 1 Options...
Page 20: ...Outdoor Unit AZQS BV1 8 Split Sky Air AZQS BV1 18 8 Centre of gravity 8 1 Centre of Gravity...
Page 21: ...3 8 Split Sky Air AZQS BV1 19 Outdoor Unit AZQS BV1 8 Centre of gravity 8 1 Centre of Gravity...
Page 22: ...Outdoor Unit AZQS BV1 9 Split Sky Air AZQS BV1 20 9 Piping diagrams 9 1 Piping Diagrams...
Page 25: ...3 11 Split Sky Air AZQS BV1 23 Outdoor Unit AZQS BV1 11 Sound data 11 1 Sound Power Spectrum...
Page 29: ...3 12 Split Sky Air AZQS BV1 27 Outdoor Unit AZQS BV1 12 Installation 12 1 Installation Method...
Page 30: ...Outdoor Unit AZQS BV1 12 Split Sky Air AZQS BV1 28 12 Installation 12 1 Installation Method...
Page 32: ......