Si50-203
Airtightness Test
Semi-Hermetic Single Screw Compressor Version III
29
5. Airtightness Test
Using dry air mixed with refrigerant, pressurize to
. Then, use a gas detector (or soap water)
to check for leaks. Apply soap water on the side caps and other cover mounting sections to
make sure no air bubbles are formed. If air bubbles are formed, release the pressure, then re-
tighten the bolts. If the leak does not stop, check the packing seating surfaces and replace the
packing.
refrigerant type
R22
2.8MPa(28bar)
R134a
2.0MPa(20bar)
R407c
2.98MPa(29.8bar)