16
6.
Minimum Deadband (1°F to 9°F) (1°C to 5°C)
Set the minimum separation between heat setpoint and cool setpoint in Auto Changeover Mode.
Press the
or
to set deadband value.
Press
to advance to the next screen.
CONFIG
5.
Staged Off Outputs
Select whether the outputs for heating and cooling are staged off independently or are
satisfied simultaneously.
= Outputs off simultaneously. = Outputs staged off independently.
Note:
For 2 compressor heat pumps and multi-stage gas/oil systems, stage 3 is staged off
independently when SO is set to
.
Press the
or
to set.
Press
to advance to the next screen.
CONFIG
7.
Heat Source: There are six heat source settings:
WARNING!
:
Incorrect settings can damage system and/or cause potentially dangerous conditions. Use the code
described in Configuration and Thermostat Lock.
CONFIG
Note:
Daikin Water Source Heat Pumps require setting “9” for proper operation.
Water Source Heat Pump
8.
Auxiliary Delay ON (0-60 minutes)
Set the delay time in minutes for auxiliary heat to be locked out after a call for second stage. This
extra savings feature is used to temporarily lock out auxiliary heat devices, allowing just heat pump to
try to satisfy heat call.
Press the
or
to select.
Press
to advance to the next screen.
CONFIG
HEAT