IM 955-3 / Page 5 of 6

Timed Override Button Test

1.  Using the BMS, change the room settings so the unit is in 

Unoccupied mode.

2.  Press the room sensor mounted override push button for 

more than 3 seconds and less than 10 seconds.

3.  Unit will resume Occupied operation until the override 

time expires ( as programmed in BMS).

4.  Using the BMS, return the unit to regular schedule.

Figure 3: MicroTech III Wall Sensor 669529101 (669529201 

- Similar)

Fan Control

Slide Switch

Mode Control

Slide Switch

Status LED

(Green)

0 to 1.5 K ohm

Potentiometer

Tenant Override

Momentary Push Button Switch

4.59"

3.75"

Temperature Sensor – 669529001

Cool Test

1.  Using the building automation system (BMS), adjust 

room cooling setpoint to 5 degrees below room 

temperature.

2.  Air conditioning should come on within five (5) minutes. 

Status indicator may come on.

3.  Using the BMS, adjust the set temperature 2 degrees 

above the room temperature and the A/C should turn off. 

There may be a fan delay on your system.

Heat Test

1.  Using the building automation system (BMS), adjust 

room heating setpoint to 5 degrees above room 

temperature.

2.  Heating should come on within five (5) minutes. Status 

indicator may come on.

3.  Using the BMS, adjust the set temperature 2 degrees 

above the room temperature and the A/C should turn off. 

There may be a fan delay on your system.

Table 2: WSHP Unit Status LED Definitions

Status LED

Unit Status

Unit Operation

ON

OFF

0.5 seconds

0.5 seconds

Controller Off  

(or Network “Wink” 
operation active)

“Alarm”

0.0 seconds

Continuous

Unit running in Night 

Setback Override 
Mode or no power to 

the sensor

“Override”

0.5 seconds

5.5 seconds

Unoccupied Mode

“Unoccupied”

5.5 seconds

0.5 seconds

Standby Mode

“Energy Save” or 
“Load Shed” com

-

mand from Energy 
Management System

Continuous

0.0 seconds

Occupied Mode

“Occupied”

Figure 4: MicroTech III Wall Sensor

3.28"

4.5"

Operating Modes

Temperature Sensors 669529101 & 669529201

Cool Mode

■  In cool mode the MicroTech III wall-mounted  

temperature sensor controls the cooling system

Heat Mode

■  In heat mode, the Microtech III wall-mounted Room 

Temperature Sensors controls the heating system.

Auto-changeover Mode

■   In this mode the Microtech III wall-mounted Room 

Temperature Sensors will automatically change from heat 

mode to cool mode, or vice versa. 

All Temperature Sensors 

Timed Override

■  Press Override button for more than 3 but less than 10 

seconds and Unit will return to Occupied operation until 

the override time expires ( as programmed in BMS).

Summary of Contents for 669529101

Page 1: ...ce Heat Pump Wall Mounted Room Temperature Sensors Sensor Kit P N 669529101 669529201 669529001 Group WSHP Part Number 910144730 Date October 2013 IM 955 3 Sensor 669529101 Sensor 669529201 Sensor 669529001 2013 Daikin Applied www DaikinAP com 800 432 1342 ...

Page 2: ...Microtech III Wall Mounted Room Tem perature Sensor For installation and commissioning instructions and general information on a particular unit refer to its model specific installation manual Table 1 MicroTech III Sensor Kits Water Source Heat Pump 10 kW Sensor Kit P N Tenant Override Button SPT Adj Pot Status LED Fan and Mode Switches 669529001 Yes No Yes No 669529101 Yes Yes Yes Yes 55º to 95ºF...

Page 3: ...njury or death 1 Turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position 2 Remove the sensor cover by inserting a screwdriver and gently twisting it in the slots on the sides of the wall temperature sensor 669529101 669529201 only To remove the cover on sensor 669529001 loosen two allen wrench set screws located on the undersid...

Page 4: ...ot affect wiring Figure 1 Temperature Sensor Wiring to MicroTech III Unit Controller Temperature Sensor Terminals MicroTech III Unit Con troller TB1 Terminals Temperature Sensor 669529001 Figure 2 Temperature Sensor Wiring to MicroTech III Unit Controller MicroTech III Unit Con troller TB1 Terminals Temperature Sensor Terminals Testing Temperature Sensors 669529101 669529201 Cool Test 1 Slide Mode...

Page 5: ...ve 5 minutes Status indicator may come on 3 Using the BMS adjust the set temperature 2 degrees above the room temperature and the A C should turn off There may be a fan delay on your system Table 2 WSHP Unit Status LED Definitions Status LED Unit Status Unit Operation ON OFF 0 5 seconds 0 5 seconds Controller Off or Network Wink operation active Alarm 0 0 seconds Continuous Unit running in Night S...

Page 6: ...s at www DaikinAP com and click on Training or call 540 248 9646 and ask for the Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 430285Y To find your local Daikin Representative go to www DaikinAP com Aftermarket Services...

Reviews: