Refrigerant piping work
5.
Charging refrigerant
1) If the total length of piping for all rooms exceeds the figure listed below, additionally charge with
20g
of refrigerant (R32) for
each additional meter of piping.
CAUTION
Even though the stop valve is fully closed, the refrigerant may slowly leak out; do not leave the flare nut removed for a long
period of time.
Precautions for compressor
Outdoor capacity class
3MXM40*, 3MXM52*, 3AMXM52*, 3MXM68*,
4MXM68*, 4MXM80*, 5MXM90*
Total length of piping for all rooms
30 m
WARNING
Electric shock hazard
• Use this compressor on a grounded system only.
• Turn power OFF before servicing.
• Replace terminal cover before applying power.
Injury hazard
• Wear protective goggles.
Explosion or fire hazard
• Use tubing cutter to remove compressor.
• Do NOT use torch. System contains refrigerant under pressure.
• Do NOT drive under air or vacuum condition.
• Use only approved refrigerants and lubricants.
Burn hazard
• Do NOT touch with bare hands during or immediately after operation.
6
5
Please fill in with indelible ink,
the factory refrigerant charge of the product,
tCO
2
eq calculation according to the formula (rounded up
to 2 decimal places)
the additional refrigerant amount charged in the field and
the total refrigerant charge
on the refrigerant charge label supplied with the product.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases.
Do not vent gases into the atmosphere.
Refrigerant type:
GWP
value:
Factory refrigerant charge of the
product:
see unit name plate
Additional refrigerant amount
charged in the field
Total refrigerant charge
Quantity of fluorinated
greenhouse gases
of the total
refrigerant charge expressed
as tonnes CO
2
equivalent.
Outdoor unit
Refrigerant cylinder and manifold
for charging
The filled out label must be adhered in the
proximity of the product charging port
(e.g. onto the inside of the stop valve cover).
GWP = global warming potential
(1)
(1)
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: 675
675
R32
R32
NOTE
National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit.
Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit. Sticking instructions are illustrated on the backside of that label.
NOTICE
Applicable legislation on
fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated both in weight and
CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes:
GWP value of the refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label. That GWP is based on the current legislation on fluorinated greenhouse
gases. The GWP mentioned in the manual might be outdated.