Trial Operation and Testing
•
Before starting the trial operation, measure the voltage at the primary side of the circuit breaker.
•
Check that all liquid and gas stop valves are fully open.
•
Check that piping and wiring all match. The wiring error check can be conveniently used for underground wiring and other wiring
that cannot be directly checked. However, if the outside air temperature is
41°F (5°C) or less
, the wiring error check function
will not operate.
1.
Wiring error check
This product is capable of automatic correction of wiring errors.
Press the wiring error check switch on the outdoor unit service PC-board for about
3 seconds. However, the wiring error check switch will not function for 3 minutes after the
safety breaker is turned on. About 15-20 minutes after the switch is pressed, the errors in
the connection wiring will be corrected.
The service monitor LEDs indicate whether or not correction is possible, as
shown in the table below. For details on how to read the LED display, refer to
the collective indications label on the reverse side of the top plate or the service
manual.
If self-correction is not possible, check the indoor unit wiring and piping in the usual
manner.
Service PC-board
A
1
2
3
4
5
Wiring error
check switch
(SW3)
LED
Status
1
2
3
4
All
Flashing
Automatic correction impossible
Automatic correction completed
Abnormal stop [Note. 3]
Message
Flashing
One after another
(One or more of LEDs 1 to 4 are ON)
Terminal block
Wiring error check
LED lighting sequence after a wiring correction.
Order of LED flashing
: 2 1 3 4
From Room C
to the “kitchen”
From Room B
to the “living room”
From Room D
to the “children’s room”
From Room A
to the “bedroom”
Wiring correct example
The figure at left sh
ows branch wiring.
NOTE
1)
For two rooms, LED 3,4 and 5 are not displayed, and for three rooms, LED 4 and 5 is not displayed, and for four rooms,
LED 5 is not displayed.
2)
After wiring error check operation is completed, LED indication will continue until ordinary operation starts. This is normal.
3) Follow the product diagnosis procedures. (Details of product error diagnosis are listed on the reverse side of the top plate.)