Outdoor Unit Installation Guideline

• Where a wall or other obstacle is in the path of outdoor unit’s inlet or outlet airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.

Selecting a Location for Installation of 

the Indoor Units

• The maximum allowable length of refrigerant piping, and the maximum allowable height difference between the outdoor and 

indoor units, are listed below.
(The shorter the refrigerant piping, the better the performance. Connect so that the piping is as short as possible. 

Shortest allow-

able length per room is 3m.

Piping to each indoor unit

20m max.

Total length of piping between all units

30m max.

If the outdoor unit is positioned higher than the 
indoor units.

If the outdoor unit is positioned otherwise.
(If lower than one or more indoor units.)

More than 50

More than 100

Side view

Direction 
of air

1200
or less

Wall facing one side

Top view

More than 150

More than 300

More than 50

unit: mm

Walls facing three sides

Top view

More than 50

More than 50

More than 150

More 
than 100

Walls facing two sides

Level  
difference: 
15m max.

Level  
difference: 
7.5m max.

Indoor Unit

Outdoor Unit

Level 
difference: 
7.5m max.

Level  
difference: 
15m max.

Outdoor Unit

Indoor Unit

Summary of Contents for 2AMXM40M2V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models 2MXM40M2V1B 2MXM50M2V1B 2AMXM40M2V1B 2AMXM50M2V1B Deutsch Fran ais Nederlands Espa ol Italiano Portugues T rk e...

Page 2: ......

Page 3: ...blece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A...

Page 4: ...ionsfilen D som positivt intygats av E Fastsatt modul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifi...

Page 5: ...survele PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22...

Page 6: ...es may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be secure...

Page 7: ...e malfunctions smoke or fire Please instruct the customer to keep the area around the unit clean The temperature of refrigerant circuit will be high please keep the inter unit wire away from copper pi...

Page 8: ...y be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air condi...

Page 9: ...prevent air from getting in between the copper piping and the insulation tube Be sure to do this if the outdoor unit is installed above Cut thermal insulation pipe to an appropriate length and wrap it...

Page 10: ...on bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their ends are 20mm from the foundation...

Page 11: ...formance Connect so that the piping is as short as possible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor...

Page 12: ...joints which have been used once already Installation shall be done by an installer the choice of materials and installation shall comply with the applicable legislation In Europe the EN378 is the ap...

Page 13: ...high pressure valve Hi 3 Apply vacuum pumping for 20 minutes or longer Check that the compound pressure gauge reads 0 1MPa 76cmHg 4 After checking the vacuum close the low pressure and high pressure v...

Page 14: ...ill break the compressor 3 5 6 2 1 4 R32 Please fill in with indelible ink 1 the factory refrigerant charge of the product 2 the additional refrigerant amount charged in the field and 1 2 the total re...

Page 15: ...pe 4 Flare the pipe 5 Check that the flaring is properly made WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the un...

Page 16: ...nuously The units in both rooms will start 2 Forced cooling operation will end after around 15 minutes and the unit will stop automatically Press the start stop button on the indoor unit to force the...

Page 17: ...the stranded wires must be used make sure to use the round crimp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered p...

Page 18: ...MISTOR DS DIPSWITCH RC RECEIVER E H HEATER S C LIMITSWITCH F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S L FLOATSWITCH FG CONNECTOR FRAMEGROUND S NPH PRESSURESENSOR HIGH H HARNESS S NPL PR...

Page 19: ...s 1 Remove the two screws on the side and remove the top plate of the outdoor unit 2 Remove the electric box cover by sliding it being careful not to bend the electric box hook 3 Cut the jumper J23 of...

Page 20: ...unction turns off power supply to the outdoor unit and sets the indoor unit into standby electricity saving mode thus reducing the power consumption of the air conditioner The standby electricity savi...

Page 21: ...t the manual included with the indoor unit Instruct the customer how to operate the unit correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when th...

Page 22: ...eller fan ON heating Muffler 9 5CuT 9 5CuT 9 5CuT Branch pipe Muffler Gas stop valve Muffler Gas stop valve 9 5CuT 9 5CuT Thermistor gas Thermistor liquid Thermistor gas 6 4CuT 6 4CuT EV A EV B Motor...

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ...3P423316 1B 2015 12 Copyright 2015 Daikin...

Reviews: