AGZ 025D through 190D
OMM 1166-1
Digital Outputs
Description
Output Off
Output On
DO1
Compressor #2
Compressor Off
Compressor On
DO2
Compressor #4
Compressor Off
Compressor On
DO3
Compressor #6
Compressor Off
Compressor On
DO5
Circuit 2 Hot Gas Bypass SV
Solenoid Closed
Solenoid Open
DO6
Circuit 2 Liquid Line SV
Solenoid Closed
Solenoid Open
EXV Module 1 and 2
These modules will be used only when the expansion valve type is electronic.
Digital Outputs
Description
Output Off
Output On
DO1
Circuit 1 Fan Output 5
Fan(s) Off
Fan(s) On
Stepper Motor Output
Description
M1+, M1-
EXV Stepper Coil 1
M2+, M2-
EXV Stepper Coil 2
Sensor Information
Temperature
All temperature sensors will be Daikin Applied part number 1934146.
Pressure
Pressure inputs will be read using 0 to 5 volt ratiometric sensors. Nominal voltage range will be 0.5
to 4.5 volts.
Pressure on the low side will be measured using Daikin Applied part number 331764501.
Pressure on the high side will be measured using Daikin Applied part number 331764601.
Actuator Information
The electronic expansion valves used are Daikin Applied part number 33038620X. These valves
are Sporlan supplied and all use the same bipolar stepper motor.
Setpoints
Setpoints are stored in permanent memory.
SetPoint Tables
Setpoints are initially set to the values in the
Default
column, and can be adjusted to any value in the
Range
column.