27
Figure 8-2
8.4
RS485 Bus FAQ
Phenomenon Possible Reasons
Solution
Speed dome
can run self-
diagnosis but
I cannot
control it.
Host address(baud rate) and
speed dome address(baud
rate) are not match;
Positive and negative end of
RS485 Bus are
misconnected;
Connection cable is loose
;
RS485 Bus connection are
cut off;
Modify host or speed dome setup
;
Switch RS485 positive end and
negative end
;
Fix connection cable firmly
;
Replace RS485 Bus.
I can control
the speed
dome but is
not smooth
RS485 Bus connection are
not good
;
One RS485 bus is off
;
The distance between host
and speed dome is too far
;
Parallel connected too much
speed domes.
Connect RS 485 Bus again
;
Replace RS485 Bus
;
Add terminal matching resistance
;
Add RS485 distributor.