Cable Diameter (36V DC) and Transmission Distance 34
Cable Diameter (36V DC) and
Appendix 6
Transmission Distance
It is the recommended transmission distance for the fixed-sized cable with attrition rate lower
than 10% of 36V DC.
The Max. attrition rate of voltage allowed for DC power supply is 10%. The cables in the
following table are all copper cables with electrical resistivity
ρ = 0.0175Ω ∗ mm
2
/m
.
Transmission
Power
Consumption (W)
Cable Diameter (mm)
0.8000
1.000
1.250
2.000
Transmission Distance Feet (m)
5
335.03
523.48
817.94
2093.92
10
167.51
261.74
408.97
1046.96
15
111.68
174.49
272.65
697.97
20
83.76
130.87
204.48
523.48
25
67.01
104.70
163.59
418.78
30
55.84
87.25
136.32
348.99
35
47.86
74.78
116.85
299.13
40
41.88
65.43
102.24
261.74
45
37.23
58.16
90.88
232.66
50
33.50
52.35
81.79
209.39
55
30.46
47.59
74.36
190.36
60
27.92
43.62
68.16
174.49
65
25.77
40.27
62.92
161.07
70
23.93
37.39
58.42
149.57
75
22.34
34.90
54.53
139.59
80
20.94
32.72
51.12
130.87
85
19.71
30.79
48.11
123.17
90
18.61
29.08
45.44
116.33
95
17.63
27.55
43.05
110.21
100
16.75
26.17
40.90
104.70